Faults
Causes
Measures
No output signal
Cable break
Check the continuity
Deviating zero point signal
Overpressure limit exceeded
Observe the permissible overpressure safety
(see chapter "3. Specifications")
Deviating zero point signal
Operating temperature too high/low
Observe the permissible temperatures
(see chapter 3. "Specifications")
Constant output signal upon
change in pressure
Mechanical overload caused by
overpressure
Replace pressure transmitter; if it fails
repeatedly, contact the manufacturer
Signal span too small
Mechanical overload caused by
overpressure
Replace pressure transmitter; if it fails
repeatedly, contact the manufacturer
Signal span varies
EMC interference sources in the
environment; for example, frequency
converter
Shield the pressure transmitter; cable shield;
remove source of interference
Signal span varies/inaccurate
Operating temperature too high/low
Observe the permissible temperatures
(see chapter 3. “Specifications”)
Signal span drops/too small
Signal span drops/too small
Contact manufacturer and replace pressure
transmitter
If complaint is unjustified, we will charge you the complaint processing fees.
CAUTION!
If faults cannot be eliminated by means of the measures listed above, shut down the
instrument immediately, and ensure that pressure and/or signal are no longer present, and
secure the instrument from being put back into operation inadvertently. In this case, contact
the manufacturer. If a return is needed, please follow the instructions given in chapter 9.2
"Return".
8. Faults
8. Faults
In the event of any faults, first check whether the pressure transmitter is mounted correctly, mechani-
cally and electrically.