MODBUS Programmable I/O NA-9379
FnIO S-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr
• Input Process Image Mode#1
(Status(1word) + Compressed Input Processing Data)
Addr.
#15
#14
#13
#12
#11
#10
#9
#8
#7
#6
#5
#4
#3
#2
#1
#0
0x0000
EW
0
0
0
0
0
0
0
FP
Internal protocol Status
0x0001
Analog Input Ch0 high byte (Slot#3)
Analog Input Ch0 low byte (Slot#3)
0x0002
Analog Input Ch1 high byte (Slot#3)
Analog Input Ch1 low byte (Slot#3)
0x0003
Analog Input Ch0 high byte (Slot#8)
Analog Input Ch0 low byte (Slot#8)
0x0004
Analog Input Ch1 high byte (Slot#8)
Analog Input Ch1 low byte (Slot#8)
0x0005
Discrete In low 8pts (Slot#4)
Discrete In 8pts (Slot#2)
0x0006
Discrete In 8pts (Slot#6)
Discrete In high 8pts (Slot#4)
0x0007
Discrete In high 8pts (Slot#9)
Discrete In low 8pts (Slot#9)
0x0008
Discrete In 4pts
(Slot#10)
Discrete In 4pts
(Slot#7)
Discrete In 4pts
(Slot#5)
Discrete In 4pts
(Slot#1)
Input Assembly Priority :
1) Analog Input Data (Word type)
2) 8 or 16 points Discrete Input Data (Byte type)
3) 4 points Input Data (Bit type)
4) 2 points Input Data (Bit type)
•
Input Process Image Mode#2
(Uncompressed Input Processing Data without Status)
,
default input image
Addr.
#15
#14
#13
#12
#11
#10
#9
#8
#7
#6
#5
#4
#3
#2
#1
#0
0x0000
Discrete In 8pts (Slot#2)
Empty, Always 0
Discrete In 4pts (Slot#1)
0x0001
Analog Input Ch0 high byte (Slot#3)
Analog Input Ch0 low byte (Slot#3)
0x0002
Analog Input Ch1 high byte (Slot#3)
Analog Input Ch1 low byte (Slot#3)
0x0003
Discrete In high 8pts (Slot#4)
Discrete In low 8pts (Slot#4)
0x0004
Discrete In 8pts (Slot#6)
Empty, Always 0
Discrete In 4pts (Slot#5)
0x0005
Analog Input Ch0 low byte (Slot#8)
Empty, Always 0
Discrete In 4pts (Slot#7)
0x0006
Analog Input Ch1 low byte (Slot#8)
Analog Input Ch0 high byte (Slot#8)
0x0007
Discrete In low 8pts (Slot#9)
Analog Input Ch1 high byte (Slot#8)
0x0008
Empty, Always 0
Discrete In 4pts
(Slot#10)
Discrete In high 8pts (Slot#9)
• Input Process Image Mode#3
(Compressed Input Processing Data without Status)
Addr.
#15
#14
#13
#12
#11
#10
#9
#8
#7
#6
#5
#4
#3
#2
#1
#0
0x0000
Analog Input Ch0 high byte (Slot#3)
Analog Input Ch0 low byte (Slot#3)
0x0001
Analog Input Ch1 high byte (Slot#3)
Analog Input Ch1 low byte (Slot#3)
0x0002
Analog Input Ch0 high byte (Slot#8)
Analog Input Ch0 low byte (Slot#8)
0x0003
Analog Input Ch1 high byte (Slot#8)
Analog Input Ch1 low byte (Slot#8)
0x0004
Discrete In low 8pts (Slot#4)
Discrete In 8pts (Slot#2)
0x0005
Discrete In 8pts (Slot#6)
Discrete In high 8pts (Slot#4)
0x0006
Discrete In high 8pts (Slot#9)
Discrete In low 8pts (Slot#9)
0x0007
Discrete In 4pts
(Slot#10)
Discrete In 4pts
(Slot#7)
Discrete In 4pts
(Slot#5)
Discrete In 4pts
(Slot#1)
* S-Series uses the byte-oriented register mapping.
* Size of input image bit is size of input image register *16.
Status
(1word)