Interface specification, Fnio s-series – Beijer Electronics NA-9379 User Manual
Page 12

12
MODBUS Programmable I/O NA-9379
FnIO S-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr
3.2.
Interface Specification
Programmable Specification
Programming
CoDeSys V3.5 SP3 Patch 1
Program Memory
512 Kbytes
Data Memory
512 Kbytes
%IW0~%IW639 (640 word Input and Internal memory)
%QW0~%QW639 (640 word Output and Internal memory)
%MW0~%MW639 (640 word Internal memory)
Non-Volatile Memory
32 Kbytes (Retain : 16Kbytes, Flag : 16Kbytes
Run-Time system
Multiple PLC Task
Program Languages
IEC 61131-3 (LD, IL, ST, FBD, SFC)
RTC
Retain Time : 6 days
Accuracy : <2min/month
Max. Task
2
Max. Cycle Task
2
Max. Status Task
1
Process Time
3us (100Instruction)
Interface Specification
Adapter Type
Master & Slave Node (MODBUS TCP)
Max. Expansion Module
32 slots
Max. Input Size
126 Words (252 Byte)
Max. Output Size
126 Words (252 Byte)
Max. Nodes
Limited by Ethernet Specification
Baudrate
10/100Mps, Auto-negotiation, Full Duplex
Interface Connector
RJ-45 socket * 2pcs
Protocol
MODBUS TCP, DHCP, BOOTP, SNMP
Max. Socket
18 (UDP : 6, TCP : 12, TCP_LISTEN : 6)
Other Serial Port
RS232/485 for MODBUS RTU, Touch Pannel or IOGuide
Serial Configuration (RS232/485)
Node : 1(default)
Baudrate : 38400(default)
Data bit : 8(default)
Parity bit : No parity(default)
Stop bit : 1(default)
Indicator
4 LEDs
(NET LED is Not used)
1 Green/Red, Module Status (MOD)
1 Green/Red, Run Status (RUN)
1 Green/Red, Extension Module Status (I/O)
1 Green, Field Power Status