Fnio s-series – Beijer Electronics NA-9379 User Manual
Page 75

75
MODBUS Programmable I/O NA-9379
FnIO S-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr
A.4.5. Adapter Setting Special Register (0x1600, 5632)
Address
Access
Type, Size
Description
0x1600(5632)
Read
2word
IP Address. (ex : C0A8 6464 = 192.168.100.100)
0x1602(5634)
Read
2word
Subnet Mask. (ex : FFFF FF00 = 255.255.255.0)
0x1604(5636)
Read
2word
Gate way. (ex : C0A8 0001 = 192.168.0.1)
0x1606(5638)
Read/Write 1word
RS-232 Baudrate. (1200bps~115200bps)
1 : 2400 2 : 4800 3 : 9600 4 : 19200
5 : 38400 (default) 6 : 57600 7 : 115200
0x1607(5639)
Read/Write 1word
RS-232 Setting.
- 1 nibble : Data bit(0 : 8bit(default), 1 : 9bit)
- 2 nibble : Stop bit(0 : 1bit(default), 1 : 2bit)
- 3 nibble : Parity bit(0 : none(default), 1: even, 2 : odd)
- 4 nibble : Reserve
0x1608(5640)
Read/Write 1word
RS-485 Baudrate. (1200bps~115200bps)
1 : 2400 2 : 4800 3 : 9600 4 : 19200
5 : 38400 (default) 6 : 57600 7 : 115200
0x1609(5641)
Read/Write 1word
RS-485 Setting.
- 1 nibble : Data bit(0 : 8bit(default), 1 : 9bit)
- 2 nibble : Stop bit(0 : 1bit(default), 1 : 2bit)
- 3 nibble : Parity bit(0 : none(default), 1: even, 2 : odd)
- 4 nibble : Reserve
0x160A(5642)
Read/Write 1word
MODBUS Station.
- High 1byte : Station No. of RS-232C (default : 1)
- Low 1byte : Station No. of RS-485 (default : 1)
0x160B(5643)
Read/Write 1word
IP Setting Method.
- Not Use : 0x0000 - BootP : 0x8000 (default)
- DHCP : 0x8001
0x1610(5648)
Read
3word
Mac Address (ex : 0014 F700 0101 = 00.14.F7.00.01.01)
0x1620(5664)
Read/Write 4word
RTC
- 1 word : 00ss (ss : sec)
- 2 word : hhmm (hh : hour, mm : min)
- 3 word : mmdd (mm : month, dd : day)
- 4 word : yyyy (yyyy : year)
(ex : 07D8 0514 0F19 0006 = 2008. 05.20. 15.25. 06)