MODBUS Programmable I/O NA-9379

FnIO S-Series



Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr

A.4.4. Adapter Information Special Register (0x1100, 4352)

Address

Access

Type, Size

Description

0x1100(4352)

Read/Write

1 word

Reserved.

0x1101(4353)

Read

1 word

Reserved.

0x1102(4354)

Read

1 word

Start address of input image word register. =0x0000

0x1103(4355)

Read

1 word

Start address of output image word register. =0x0800

0x1104(4356)

Read

1 word

Size of input image word register.

0x1105(4357)

Read

1 word

Size of output image word register.

0x1106(4358)

Read

1 word

Start address of input image bit. = 0x0000

0x1107(4359)

Read

1 word

Start address of output image bit. =0x1000

0x1108(4360)

Read

1 word

Size of input image bit.

0x1109(4361)

Read

1 word

Size of output image bit.

0x110D(4365)

Read/Write

1word

Enable/Disable Auto Reboot when expansion module,
0:Disable(Default)

0x110E(4366)

Read

Up to 33 word

Expansion slot’s ST-number including NA
First 1word is adapter’s number, if NA-9379, then 0x9379

0x1110(4368)

Read

1 word

Number of expansion slot

0x1111(4369)

Read

1 word

Number of active slot

0x1112(4370)

Read

1 word

Number of inactive slot

0x1113(4371)

Read

Up to
33 word

Expansion slot Module Id. Refer to Appendix B.1 Product List.
First 1word is adapter’s module id.

0x1114(4372)*

Read/Write

1 word

Input process image mode. The default value is 2.
Valid value range is from 0 to 3.

0x1115(4373)*

Read/Write

1 word

Output process image mode. The default value is 0.
Valid value range is from 0 to 1.

0x1116(4374)**

Read/Write

2 words

Inactive slot list, The corresponding bit represents slot position.
0: Active slot, 1: Inactive slot.
Ex) if value is 0x0001, 0x8000, then slot#1,#32 are inactive slots

0x1117(4375)

Read

2 words

Live slot list. , The corresponding bit represents slot position.
1: live slot, 0: not live slot

0x1118(4376)

Read

2 words

Alarm slot list. The corresponding bit represents slot position.
1: Alarm slot, 0: Normal slot

0x1119(4377)

Read

1 word

Hi byte is MODBUS status, low byte is expansion module status.
It is identical with address 0x1040.

0x111A(4378)

Write

1 word

Reserved. Adapter Scan command.

0x111B(4379)

Read/Write

1 word

Reserved. IO State machine.

0x111C(4380)

Read

2 words

Reserved. Runtime fault code.

0x111D(4381)

Read

1 word

Adapter Revision. If 0x013C, Revision is 1.60

0x111E(4382)

Read

1 word

Reserved. Adapter IO identification vendor code.

0x111F(4383)

Read

5 word

LED Display Value and Status Code

* After the system is reset, the new “Set Value” action is applied.
* If the slot location is changed, set default value automatically (all expansion slots are live).