A.J. Antunes & Co FGM-H150 8271007150 User Manual
Versa plus gas pressure switches, Dimensions, Ranges available specifications
1-630-784-1000 Fax: 630-784-1651
Page 1 of 4
P/N 1011063 Rev. B 06/12
1-800-253-2991
A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
Versa Plus Gas Pressure Switches
Versa Plus Gas Pressure Switches by Antunes Controls
monitor gas pressure and break the electrical control
circuit when pressure drops below or rises above the
desired setpoint. The gas pressure settings are adjustable
and available in manual or automatic reset operation.
These switches are sturdy and constructed with a dura-
ble plastic electrical enclosure and a die-cast aluminum
inlet base.
Dimensions
IMPORTANT
Please read these instructions carefully to assure
correct installation. This equipment must be
installed only by a licensed electrician who is
experienced with combustion safeguard control
systems and understands the functions of inter-
locking switches, such as gas pressure switches.
Prior to being put into operation in conjunction
with the combustion safeguard systems, all
switches should be tested for proper range setting
and proper wiring. Check piping connections and
switch house for leaks with a soap bubble test. All
exhaust fans and blowers should be inspected and
checked for proper rotation prior to starting up.
Versa Plus Gas Pressure Switches Installation Information
Gas (Air) Inlet 1/4" NPT
3"
(76 mm)
2 11/16"
(68 mm)
3"
(76 mm)
1 3/8"
(35 mm)
1 11/16"
(43 mm)
13/16"
(21 mm)
1 5/32"
(30 mm)
3"
(76 mm)
Reset Buttom
(Manual Only)
1/2" Conduit
Knockout
Gas (Air) Inlet 1/4" NPT
3"
(76 mm)
2 11/16"
(68 mm)
3"
(76 mm)
1 3/8"
(35 mm)
1 11/16"
(43 mm)
13/16"
(21 mm)
1 5/32"
(30 mm)
3"
(76 mm)
Reset Buttom
(Manual Only)
1/2" Conduit
Knockout
Gas (Air) Inlet 1/4" NPT
3"
(76 mm)
2 11/16"
(68 mm)
3"
(76 mm)
1 3/8"
(35 mm)
1 11/16"
(43 mm)
13/16"
(21 mm)
1 5/32"
(30 mm)
3"
(76 mm)
Reset Buttom
(Manual Only)
1/2" Conduit
Knockout
Ranges Available
Specifications
Electrical Ratings: 6A @ 120 VAC, 6A @ 240 VAC, 1/8
HP 120 & 240 VAC
Adjustable Operating Pressure: 1.2 to 150 mbar
0.5" W.C. to 60" W.C. (different ranges)
NOTE: To avoid initial line fill pressure spikes, unit should
be placed downstream of the regulator.
Max. Surge Pressure: 7 PSI (482 mbar)
Ambient Operating Temperature: 5°F to 180°F
(-15°C to 82°C)
Field wiring to be rated @ 90°C (194°F) for maximum
ambient
Shipping Weight: 0.5 lbs. (.227 kg)
Options:
4-Pin DIN Connector
Neon Lamp Indicator
Side Mounting
Low Ranges
Model
Part No.
W.C.
mbar
Automatic Reset
FGA-L010
8261001010
0.5"–4"
1.2–10
FGA-L050
8261002050
1"–20"
2.5–50
FGA-L110
8261003110
5"–44"
12–110
Manual Reset
FGM-L 010
8271001010
0.5"–4"
1.2–10
FGM-L 050
8271002050
1"–20"
2.5–50
FGM-L 075
8271003075
5"–30"
12-75
FGM-L 136
8271004136
7"–55"
17-136
High Ranges
Model
Part No.
W.C.
mbar
Automatic Reset
FGA-H010
8261005010
0.8"–4"
2–10
FGA-H050
8261006050
2"–20"
5–50
FGA-H087
8261007087
5"–35"
12–87
Manual Reset
FGM-H 050
8271005050
2"–20"
5–50
FGM-H 087
8271006087
8"–35"
20–87
FGM-H 150
8271007150
10"–60"
25–150
Note: Dimensions are