A.J. Antunes & Co FAB 050 8291003050 User Manual
Versa plus air pressure switches, Dimensions, Specifications

1-630-784-1000 Fax: 630-784-1651
Page 1 of 4
P/N 1011062 Rev. B 06/12
1-800-253-2991
A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
Versa Plus Air Pressure Switches
Versa Plus Air pressure switches by Antunes Controls
monitor positive, vacuum, or differential air pressures.
The integrated contacts make or break the circuit to the
desired set point. The large adjustment knob provides
set point indication and aids in ease of adjustment. The
Versa Plus Air series can be factory adjusted for applica-
tions that require other differential settings.
Dimensions
IMPORTANT
Please read these instructions carefully to assure
correct installation. This equipment must be
installed only by a licensed electrician who is
experienced with combustion safeguard control
systems and understands the functions of inter-
locking switches, such as gas pressure switches.
Prior to being put into operation in conjunction
with the combustion safeguard systems, all
switches should be tested for proper range setting
and proper wiring. Check piping connections and
switch house for leaks with a soap bubble test. All
exhaust fans and blowers should be inspected and
checked for proper rotation prior to starting up.
Versa Plus Air Pressure Switches Installation Information
Specifications
Electrical Ratings: 6A @ 120 VAC, 6A @ 240 VAC,
1/8 HP, 120 & 240 VAC. Integrated S.P.D.T. contacts.
Adjustable Operating Pressure: 0.2 to 50 mbar
(different
ranges)
Max. Surge Pressure: 7 PSI (482 mbar)
Pressure Connections: 1/8” NPT positive & vacuum
ports; 1/4” hose barb OD.
Ambient Operating Temperature: 5°F to 180°F
(-15°C to 82°C)
Field wiring to be rated @ 90°C (194°F) for maximum
ambient
Shipping Weight: 0.5 lbs. (.227 kg)
Options:
Mounting brackets can be oriented in any of the 90°
positions.
Vacuum
Inlet
1/2” Conduit
Knockout
Pressure
Inlet
3"
(76 mm)
3"
(76 mm)
2 5/16"
(59 mm)
Vacuum
Inlet
1/2” Conduit
Knockout
Pressure
Inlet
3"
(76 mm)
3"
(76 mm)
2 5/16"
(59 mm)
Model
Part No.
W.C.
mbar
NPT Switches (activate on pressure fall/vertical mount)
FAN 1.2
8281001001
.08"–.5"
0.2–1.2
FAN 010
8281002010
.5"–4"
1.2–10
NPT Switches (activate on pressure rise/horizontal mount)
FAN 050
8281003050
1"–20"
2.5–50
Hose Barb Switches (activate on pressure fall/vertical mount)
FAB 1.2
8291001001
.08"–.5"
0.2–1.2
FAB 010
8291002010
.5"–4"
1.2–10
Hose Barb Switches (activate on pressure rise/horizontal mount)
FAB 050
8291003050
1"–20"
2.5–50
Installation
All switches are tested at the factory in a vertical position.
Mounting diaphragm in vertical position is the preferred
method.
Air Connection
Tubing recommended as minimums: 1/4” copper or alumi-
num tubing, or 1/8” pipe.
All tubing and pipe must be clean and free from oil, dirt,
and chips. If piping runs over five feet long, use larger
size tubing or pipe and reduce size at switch connection.
Ranges Available
Note: Dimensions are for reference only.