Campbell Scientific CS105/CS105MD Barometric Pressure Sensor User Manual

Page 12

background image

CS105/CS105MD Barometric Pressure Sensor

07: Real Time (P77)
1: 0110

Day,Hour/Minute


08: Sample (P70)
1: 1

Reps

2: 1*

Loc [ P_mb ]


-Input Locations-
1 P_mb

*

Proper entries will vary with program and datalogger channel, and input location assignments.

** On the 21X use the 5000 mV slow range.

Example 3. CR10(X) Program for Measuring the CS105 Every Execution Interval

;{CR10X}
;
*Table 1 Program
01: 2

Execution

Interval

(seconds)


01: Do (P86)
1: 41*

Set Port 1* High


02: Excitation with Delay (P22)
1: 1

Ex

Channel

2: 0

Delay W/Ex (units = 0.01 sec)

3: 100

Delay After Ex (units = 0.01 sec)

4: 0

mV

Excitation


03: Volts (SE) (P1)
1: 1

Reps

2: 25**

± 2500 mV 60 Hz Rejection Range

3: 7*

SE

Channel

4: 1*

Loc [ P_mb ]

5: .184

Mult

6: 600

Offset


04: Do (P86)
1: 51*

Set Port 1* Low


05: If time is (P92)
1: 0

Minutes (Seconds --) into a

2: 30

Interval (same units as above)

3: 10

Set Output Flag High (Flag 0)


06: Real Time (P77)
1: 0110

Day,Hour/Minute


07: Average (P71)
1: 1

Reps

2: 1*

Loc [ P_mb ]

8