CS105/CS105MD Barometric Pressure Sensor

Example 1. CR1000 Program for Measuring the CS105 Once Every Hour

'Main Program
BeginProg
Scan(5,Sec,1,0)
'CS105

Barometric

Pressure Sensor measurement BP_mmHg:

If IfTime(59,60,Min) Then PortSet(1,1)

If

IfTime(0,60,Min)

Then

VoltSE(BP_mmHg,1,mV2500,1,1,0,_50Hz,0.184,600.0)
BP_mmHg=BP_mmHg*0.75006
PortSet(1,0)
EndIf

'Call Data Tables and Store Data

NextScan
EndProg

Example 2. CR10(X) Program for Measuring the CS105 Once Every Hour

;{CR10X}
;
*Table 1 Program
01: 30

Execution

Interval

(seconds)


01: If time is (P92)
1: 59

Minutes (Seconds --) into a

2: 60

Interval (same units as above)

3: 41*

Set Port 1* High


02: If time is (P92)
1: 0

Minutes (Seconds --) into a

2: 60

Interval (same units as above)

3: 30

Then

Do


03: Volts (SE) (P1)
1: 1

Reps

2: 25**

± 2500 mV 60 Hz Rejection Range

3: 7*

SE

Channel

4: 1*

Loc [ P_mb ]

5: .184

Mult

6: 600

Offset


04: Do (P86)
1: 51*

Set Port 1* Low


05: End (P95)

06: If time is (P92)
1: 0

Minutes (Seconds --) into a

2: 60

Interval (same units as above)

3: 10

Set Output Flag High (Flag 0)

7