beautypg.com

1 com terminals, 2 sensor input terminals, Com terminals – Campbell Scientific AM16/32B Relay Multiplexer User Manual

Page 21: Sensor input terminals, Using cable4cbl cable, Figure 4-4), 1 com termin, 2 sensor inpu, T terminals, Am16/32b relay multiplexer

background image

AM16/32B Relay Multiplexer

4.2.1 COM Termin

ue COM next to the mode switch. The terminals are labeled: ODD

s

als

A CABLE3CBL, CABLE4CBL, or CABLE5CBL cable is used to connect the
datalogger to the COM terminals. The CABLE3CBL is recommended when
the AM16/32B is used in the 4x16 mode. The CABLE4CBL is typically used
for the 4x16 mode. The CABLE5CBL is recommended for the 4x16 mode
when it is desirable to connect both shields.

The four terminals dedicated to multiplexer-datalogger connection are located
under the bl
H, ODD L, EVEN H, and EVEN L. In “4x16” mode the AM16/32B maintain
the four COM terminals electrically isolated from one another. In “2x32”
mode, the AM16/32B maintains an internal connection between ODD H and
EVEN H and between ODD L and EVEN L.

Common “

” terminals are provided next to the COM ODD and COM EVEN

terminals. They bus internally to the

other thirty-two “ ” terminals on the

AM16/32B and are connected at all times (not switche

Their function is to

provide a path to ground for sensor cable shields. A C

d).
OM

terminal should

be wired to datalogger ground via the cable’s shield according to the following
table.

COM

ODD

4X16

H

L

EVEN

H

L

O

N

MUXSIGNAL

SHIELD

CR10X

CR23X

CR1000

CR3000,

CR5000

21X

CR7

CR800,

CR850

G

CABLE

E1-E3 EX1-EX4

EX1-EX3

or

VX1-VX3

VX1-VX4 EXCITATION SWITCHED

ANALOG OUT

EX1-EX2 or

VX1-VX2

SE3 SE3 SE3 SE3

2H

2H

SE3

SE2 SE2 SE2 SE2

1L

SE2

1L

SE1 SE1 SE1 SE1

1H

1H

SE1

FIGURE 4-4. Typical AM16/32B to datalogger signal hookup (4x16

mode) using CABLE4CBL cable

4.2.2 Sensor Inpu

In “4x16” mode, the odd numbered terminals (example: 5H, 5L) are relay
switched to the COM ODD terminals while the even terminals (6H, 6L) are
switched to the COM EVEN terminals. When activated by the RES line being
high, as the AM16/32B receives clock pulses from the datalogger, each SET of
four in turn is switched into contact with the four COM terminals. For
example, when the first clock pulse is received from the datalogger, SET 1

t Terminals

The terminals for sensor attachment are divided into 16 groups (panel switch
set to “4x16”) or into 32 groups (panel switch set to “2x32”). The groups
consist of four or two Simultaneously Enabled Terminals (SETs). With panel
switch set to “4x16” mode, the blue channel numbers apply. The SETs are
numbered starting at 1 (1H, 1L, 2H, 2L) and continuing until SET 16 (31H,
31L, 32H, 32L).

11