2 control port programming, 1 cr1000 programming, 2 cr200 series programming – Campbell Scientific 380, 385, 380M, 385M Met One Rain Gages User Manual
Page 16

Met One Rain Gage Models 380 and 385
‘Main Program
BeginProg
Scan(10,Sec,1,0)
‘Default Datalogger Battery Voltage measurement Batt_Volt:
Battery(Batt_Volt)
‘MetOne 380/385 Rain Gauge measurement Rain_in:
PulseCount(Rain_in,1,1,2,0,0.01,0)
‘Call Data Tables and Store Data
CallTable(Table1)
CallTable(Table2)
NextScan
EndProg
5.2 Control Port Programming
The following examples measure a 380 and 385 rain gage using a control port
on a datalogger. Wire the sensor as shown in Table 4-2.
5.2.1 CR1000 Programming
'CR1000
'Declare Public Variables and Units
Public Rain_in
Units Rain_in=inch
DataTable (Rain,True,-1)
DataInterval
(0,60,Min,0)
Totalize
(1,Rain_in,FP2,0)
EndTable
'Main Program
BeginProg
Scan
(1,Sec,1,0)
PulseCount
(Rain_in,1,18,2,0,.01,0) ; Black wire connect to C8
CallTable
(Rain)
NextScan
EndProg
5.2.2 CR200 Series Programming
'CR200
'A 20 kOhm pull up resistor is required to read a switch closure on C1 or C2
'as a Pulse Counter. The 20 kOhm resistor uses the battery voltage.
'Declare Public Variables and Units
Public Rain_in
Units Rain_in=inch