Intended Use
Keep a printed copy of the Preface of this User’s Manual in or near the cabinet.
• Install the cabinet only in a Restricted Access Location, such as a data center.
• Use indoors only, in environmentally controlled areas; do not use outdoors, in harsh environments,
or in air-‐handling spaces.
• Use the cabinet for information technology and telecommunications equipment, including servers
and peripherals.
• Allow only qualified service personnel to use the cabinet.
• The cabinets must be anchored to the floor to ensure stability and a safe working environment.
• The load-‐bearing capacity of the Z4-‐Series SeismicFrame Cabinet is:
Static:
3,000 lb (1360 kg)*
Seismic:
1,500 lb (680 kg)**
*Tested to UL 2416, Issue 2, July 2013 Section 11.1.4, Loading test (4X rated load)
**Tested to Telcordia Technologies GR-‐63-‐CORE, Issue 4, April 2012, Sections 4.4