Safety Information
WARNINGS:
• Unload equipment from the cabinet before moving it.
• Two or more cabinets can be bayed together (coupled) to enhance their stability.
Each cabinet should be anchored to the floor.
• Before loading equipment in the cabinet, always anchor the cabinet frame to the
floor.
• Always load heavy equipment, such as a UPS, at the bottom of the cabinet first, and
add lighter equipment on higher levels.
• A safety risk exists when equipment is mounted on a shelf installed more than 30
inches (760 mm) above the floor in a cabinet without doors and/or side panels. The
equipment may accidentally slide or be accidentally pushed off the shelf and fall on
personnel. When equipment is mounted on a shelf, securely fasten the equipment
to the shelf or cabinet frame in a manner that will prevent the equipment from
accidentally sliding off the shelf. The following accessories may be used to secure
certain equipment on shelves: monitor tie-‐down kit (P/N 11725-‐701), seismic
equipment tie-‐down bracket (P/N 14061-‐719), or equipment tie-‐down bracket (P/N
16356-‐719).
• The cabinet can support many system configurations. The amount of force required
to tip or make the cabinet unstable differs with each. Read and follow your
equipment manufacturer’s specific assembly, installation, and safety instructions.
• When servicing slide-‐mounted equipment such as servers:
-
Secure all equipment, other than the unit being serviced, in position to prevent
it from sliding out and destabilizing the cabinet.
-
Slowly
extend
only
one
unit
at
a
time.
Extending
multiple
units
may
cause
the
cabinet
to
tip
over.
Rapid
deployment
of
the
unit
could
cause
the
cabinet
to
tip.
• For protection of the equipment and personnel, ground each cabinet individually to
the Telecommunications Equipment Bonding Conductor (TEBC) or Signal Reference
Structure (SRS).
• Provide the minimum spacing between the accessories/components and the
housing that shall be maintained for safe operation of the equipment when installed
in accordance with the National Electric Code, ANSI/NFPA 70.
• As appropriate, all wiring and equipment should be installed in accordance with
NFPA 70, “National Electrical Code,” and the applicable sections of ANSI C2,
“National Electrical Safety Code."