9 Error messages

Please note: Never open the device to find faults and do not

attempt to replace components yourself. Incorrectly performed

repairs can result in danger for the user and the system. This

will also invalidate all warranty claims.

When the device detects faults or impermissible operating states, this is

indicated by a flashing error code on the display.
Errors are basically either temporary faults, e.g. temporary overloading of

the device, or serious system errors that require external intervention.
Since multiple errors cannot be displayed at the same time, the error with

the highest error number (priority) is always displayed first. If multiple errors

exist, then the next error code is not displayed until the higher-priority error

has been fixed.
The error codes have the following meanings:

Display

Meaning

Cause / Remedy

Communication error

with the internal stor-

age (EEPROM).

Disconnect the load, solar

modules and battery. Re-install

the device. If the error recurs,

then please contact your

specialist dealer.

Communication error

on the external Steca

bus (6-pin edge con-

nector).

Check the plug connection

at the 6-pin edge connector,

check the power supply and

check for correct functioning

of external expansions.
If the error recurs, then please

contact your specialist dealer.

Short circuit in

external temperature

sensor.

Check the contacts of the

2-pin edge connector and

remove the short circuit.
Check sensor.

Overtemperature.

The controller has

switched off the

load due to internal

overheating.

Allow the controller to cool

down. Check for possible

causes of overheating (mount-

ing location, other heat

sources). Possibly reduce the

charging current or load cur-

rent. Make sure the controller

is adequately ventilated

Battery voltage too

low.
Voltage < 10.5 V or

< 21.0 V.

Check installation. Check the

battery voltage and manually

recharge the battery if neces-

sary. Loads directly connected

to the battery can cause deep

discharge!

Battery voltage too

high.
Voltage > 15.5 V or

> 31.0 V.

Check installation. Check the

battery voltage and check any

additional charging sources if

present.

Excessive load cur-

rent. The permissible

load current of the

controller was

exceeded, causing

the load output to be

switched off.

Reduce the load current at the

load output.
The load may cause current

peaks.
Try reconnecting the load.