Section 8 |

troubleshooting Guide

Symptom

Possible Cause

Remedy

ON / OFF Switch is ON

• Switch is lighted

• There is no voltage at the at

the load end and the load is

shut down

• Voltage at the Load Terminals

is 54.8V

• Voltage at Battery Terminals is

0.3V ± 0.1V lower than the

voltage at the Load terminals

25A Fuse (F2) in the Load circuit is

blown due to:

- Excessive short time overload

current > 25A exceeding the

Time Current Characteristics of

the 25A fuse, or

-

Short circuit in the load circuit

Remove the cause of the overload

or short circuit.

ON / OFF Switch is ON

• Switch is lighted

• Load is ON

• Voltage at the Load Terminals

is 54.8V to 54.2V

• Voltage at Battery Terminals is

the same as the Load Terminals

• Battery backup function does

not operate – Load shuts OFF
when AC power is interrupted

25A Fuse F1 in the battery circuit
is blown due to short circuit in
battery wiring or reversal of
battery polarity

Check that the polarity of battery

connections is correct. Replace

the fuse.

Check for short circuit in the

battery wiring and correct.

Replace the fuse.

GFCI outlet / GFCI breaker
supplying AC power to the
unit trips when the unit is
switched ON

Additional RF noise current from
the unit that is fi ltered to Earth
Ground increases the net Leakage
Current on the GFCI outlet / GFCI
breaker to > 5mA

Switch OFF other SMPS devices
operating from the same GFCI
outlet / GFCI breaker to reduce
the net leakage current to < 5mA.

Move the unit to another GFCI
outlet / GFCI breaker that has
lesser number of SMPS load(s) or
no SMPS load.

Power the unit from normal, non
GFCI outlet or from an outlet not
protected by GFCI breaker.

The unit is not in use. ON/OFF
Switch is OFF
• Battery is connected to the

Battery Terminals

• Load is OFF/disconnected
• Battery is getting discharged

Battery is draining by 100 mA
through the Static Load Resis-
tor connected across the Load
Terminals

Remove Battery Fuse F1 when the
unit is not in use.