beautypg.com

3 gpo, 4 protocol select jumpers – Matrix Orbital GLK12232-25-FGW User Manual

Page 14

background image

2.3

GPO

A unique feature of the GLK12232-25 is the ability to control relays and other external devices using a

General Purpose Output (3), which can provide up to 20 mA of current and +5Vdc from the positive side of
the GPO. This is limited by a 240 ohm resistor which is located directly above the positive pin as pictured
below in

figure 14

. If the device, which is being driven by a GPO, requires a relatively high current (such as

a relay) and has an internal resistance of its own greater than 250 ohms, then the 240 ohm resistor may be
removed and replaced with a Jumper.

Pin

1

- GND

Pin

2

+ MAX: 20 mA, +5Vdc

Figure 14: General Purpose Output

WARNING

If connecting a relay, be sure that it is fully clamped using

a diode and capacitor in order to absorb any electro-motive force (EMF)
which will be generated.

2.4

Protocol Select Jumpers

The Protocol Select Jumpers, pictured below in

figure 15

, provide the means necessary to toggle the

display module between RS-232, TTL and I

2

C protocols. As a default, the jumpers are set to RS-232 mode

with zero ohm resistors on the 232 jumpers. In order to place the display module in I

2

C mode you must

first remove the zero ohm resistors from the 232 jumpers and then solder the resistors on to the I

2

C jumpers.

The display will now be in I

2

C mode and have a default slave address of 0x50 unless it has been changed.

Similarly, in order to change the display to TTL mode, simply remove the zero ohm resistors from the 232
or I

2

C jumpers and solder them to the TTL jumpers.

Matrix Orbital

GLK12232-25

9