N00 non, A0 -10.0, A0- 90.0 – Ashcroft GC52 - Rangeable wet/wet Differential Pressure Transmitter User Manual
Page 21

21
No.
Setting Item
LCD Display
Setting Description
Setting Range
Default*
ቢ
Filter
Selection of
0,2,4,8,16,sec
4
moving average
timeof differential
pressure: 2 (sec)
*The factory default.
f
0000
2
For the setting procedure of each display mode, refer to paragraph 13.4.
13.1
List of Setting Items for Differential Pressure Display Mode
(Re-scaling in “inH
2
0” units). Set the filter before setting the differential
pressure setting mode. See page 24 for full menu.
non
The setting of the following table is the Setting example
1: pressure display mode of SECTION 11-2. This applies when
re-scaling in “inH
2
0” units. See page 24 for full menu.
No.
Setting Item
LCD Display
Setting Description
Setting Range
Default
ባ
n
00
non
Selection of differ-
ential pressure dis-
play mode: non
non: Differential
pressure display
mode
Lin: Linear display
mode
Display mode
-
-
0.0
ቤ
a
0
-10.0
Differential pres-
sure of analog
output zero point
4mA: –10.0(%F.S.)
Differential pres-
sure range:
–10 to 110%F.S.
Output zero
point
(1)
100.0
ብ
Differential
pressure of analog
output span point
(20mA):
90.0(%F.S.)
Differential
pressure range:
–10 to 110%F.S.
Output span
point
(1)
a
0-
90.0
0.0
(4.00
mA)
ቦ
Arbitrary change of
differential pres-
sure display and
analog output:
–10.00 (psi).)
Display: Differential
pressure display
span; Analog
output: 4 to 20mA
Loop check
(2)
[
0-
10.0
(1) For setting of zero point and span point in the analog output, input the percent value over the
differential pressure range.
(2) Regardless of generated differential pressure, the loop check can be changed by arbitrarily
linking the pressure display with the analog output using ▲, ▼ key. (Refer to Section 13.3).
This example of LCD display shows the zero point display at the time of loop check start.