– 15 –

position within the pressure range. The bottom line will

display SETPT (blinking). SETPT is switch setpoint on

rising pressure.

Note: Setpoints are limited to the full-scale pressure range

of the gauge.

Step 4: Press the

(up arrow key) or

(down arrow key)

on the keypad to increase or decrease switch set-point

Step 5: Press the ENTER key to finalize switch setpoint. The

gauge will display SET. After two seconds, the top line will

indicate RETRP pressure. The bottom line will read SET.

RETRP is switch setpoint on falling pressure.

Step 6: Repeat above to set RETRP (retrip value) If the

gauge is supplied with (1) setpoint, the screen will advance

to the measurement mode. If (2) switches are supplied the

display will advance to SW2.

Repeat the aforementioned if the gauge is supplied with

(2) switches.

Notes: The bar graph will increase or decrease as any

setpoint pressure is adjusted. The bar graph indicates

switch setpoint position within the full-scale pressure

range of the gauge.

The switch setpoint unit of pressure measurement corre-

sponds with the current set unit of measure of the gauge.

If gauge unit of measurement is changed after switch(es)

is set, switch setpoint(s) will automatically be updated to

correspond with revised unit of measurement. Switch

deadband is the difference between the SETPT (setpoint)

and the RETRP (retrip) pressure.

MENU FUNCTIONS

I&M008-10109-DIG Rev F 07-12_layout 10/14/13 9:45 AM Page 15