Ashcroft 2274 Digital Industrial Gauge User Manual
Page 15
![background image](/manuals/414152/15/background.png)
– 15 –
position within the pressure range. The bottom line will
display SETPT (blinking). SETPT is switch setpoint on
rising pressure.
Note: Setpoints are limited to the full-scale pressure range
of the gauge.
Step 4: Press the
ᮡ
(up arrow key) or
ᮢ
(down arrow key)
on the keypad to increase or decrease switch set-point
Step 5: Press the ENTER key to finalize switch setpoint. The
gauge will display SET. After two seconds, the top line will
indicate RETRP pressure. The bottom line will read SET.
RETRP is switch setpoint on falling pressure.
Step 6: Repeat above to set RETRP (retrip value) If the
gauge is supplied with (1) setpoint, the screen will advance
to the measurement mode. If (2) switches are supplied the
display will advance to SW2.
Repeat the aforementioned if the gauge is supplied with
(2) switches.
Notes: The bar graph will increase or decrease as any
setpoint pressure is adjusted. The bar graph indicates
switch setpoint position within the full-scale pressure
range of the gauge.
The switch setpoint unit of pressure measurement corre-
sponds with the current set unit of measure of the gauge.
If gauge unit of measurement is changed after switch(es)
is set, switch setpoint(s) will automatically be updated to
correspond with revised unit of measurement. Switch
deadband is the difference between the SETPT (setpoint)
and the RETRP (retrip) pressure.
MENU FUNCTIONS