beautypg.com

Part 1 installation – Midco Unipower MPG Series User Manual

Page 3

background image

The opening should be located at least six feet above ground level to prevent accidental
obstruction. If a direct opening to the outside air is not available, an amply sized air duct can be
run to the nearest outside air source or if practical, open stairwells or building corridors
connecting to an outside wall having a ventilating opening can be used for this purpose, provided
that no possibility of accidental closure exists.

While the spark ignition pilot system performs successfully under moderate or momentary

back draft conditions, it is not intended for operation under sustained reverse draft, for example,
in a building with large ventilating fans but with insufficient make-up air. Even if burner operation
is successful under these conditions, they must be corrected to prevent the hazard of drawing
flue gases into the building. Consult your local gas company when doubt exists concerning boiler
room ventilation.

___________________________

The heating system, both the gas utilization equipment and the distribution system, should be

in good operating conditions and sufficient to properly heat the building. It should be determined if
any serious faults are present that would cause excessive fuel consumption, unsafe operation or
improper heating, and measures taken to correct them.

Firing door catches should be filed off or otherwise arranged so that the door will open easily

to relieve pressure. No positive catches should be used. The use of a spring-type door holder is
recommended.

___________________________

Mount the burner to the gas utilization equipment. A tight seal between the mounting flange

and the front plate should be accomplished using the supplied high temperature rope. When
installing the gas burner the distance from the flange to the blast tube edge should be the same
as the gas utilization equipment wall thickness plus the flange gasket or rope thickness. That
means the burner blast tube will be flush with the inner chamber wall after the burner has been
installed. If the blast tube is extended into the combustion chamber possible damage to the
burner may happen. See Figure 1 & 2 for reference.

3

Part 1 Installation

II

Preparation of

the Gas Utilization

Equipment

III

Combustion

Chamber

Figure 1: Dry Base Boiler with Combustion

Chamber Liner (Warm Air Furnace

Construction is Similar)

Figure 2: Wet Base Boiler with Unlined

Combustion Chamber

Figure 3: Scotch Marine Boiler

Figure 4: Warm Air Furnaces

I

Ventilation

Continued