beautypg.com

Part 1 installation – Midco Unipower MPG Series User Manual

Page 10

background image

___________________________

The blower functions to supply a constant and positive supply of air for complete combustion.

Air volume is controlled by an adjustable shutter in the blower inlet.

No routine service is necessary on the blower other than occasionally cleaning the blower

wheel. If the blower wheel must be replaced, be sure to check the replacement for proper
rotation. The concave sides of the blades must face the blower outlet, and rotation of the wheel
must be toward the outlet. Motor sizes and specifications are given in Table 1. All motors contain
integral motor overload protection, usually manual, occasionally automatic reset.

Proof of blower operation is

provided by the diaphragm air
switch, which must close its contacts
and maintain them closed when the
blower is running. In case of
malfunction, the diaphragm air
switch must be replaced.

___________________________

A combination integrated redundant main gas valve with an integrated gas pressure regulator is
used on the standard MPG burner.

The gas pressure regulator is used to automatically reduce and maintain constant gas

pressure to the burner. To vary the outlet pressure, remove the seal cap for access to the
adjusting screw. Turning the screw clockwise will increase outlet pressure, counter-clockwise will
decrease outlet pressure.

Maximum and minimum allowable gas pressures are shown in Table 1.

___________________________

Note: All burners are equipped with dual valves. Burner construction for special codes and/or
insurance requirements such as Factory Mutual or Industrial Risk Insurers (GAP) may require
alternate construction. (Refer to Section XV Special Equipment.)

10

Part 1 Installation

XIII Main Automatic

Valves

XII

Gas Pressure

Regulator

XI

Blower and

Motor

Drawer Assembly with Flame Rod

Drawer Assembly with UV Scanner

Figure 9: Drawer Assembly MPG Burner

VIII

Initial Start-

up /Adjustment

On-Off Burners

Continued

Orifice

Orifice

Drill

Pilot Gas

Model

Type

Size "

Size

Pressure

On-Off

A

0.11"

#35

2.0"-3.5"

Low Fire Start

B

0.076"

#48

2.0"-3.5"

(Full Mod and
2-Stage)

Table 8: Pilot Gas Pressure Orifice Size

Open to 7/64" Gap