Notifier ACPS-610 User Manual
Acps-610(e), Addressable charger/power supply, General

DN-60244:C3 • 4/23/2012 — Page 1 of 2
ACPS-610(E)
Addressable Charger/Power Supply
Power Supplies
DN-60244:C3
General
The ACPS-610(E) is an auxiliary power supply with a battery
charging option and a host of special features. Selectable
charging options allow the ACPS-610(E) to provide 6 amps of
shared power to four outputs while charging batteries from
12 to 200 AH, or 10 amps of shared power when the unit is
configured for use with an external battery charger. Four indi-
vidually addressable outputs can be independently configured
for auxiliary power or Notification Appliance Circuits (NAC).
NAC outputs support notification appliance synchronization for
devices manufactured by System Sensor®, Wheelock, and
Gentex. An option to disable battery charging allows the sys-
tem designer to use the four built-in circuits to distribute
10 amps of power for general purposes, excluding NAC appli-
cations.
The ACPS-610(E) is compatible with NOTIFIER intelligent fire
alarm control panels using CLIP and FlashScan® protocol.
Features
• Certified for seismic applications when used with the appro-
priate seismic mounting kit.
• Approved for Marine applications when used with listed
compatible equipment (see DN-60688).
• Provides 6.0 A of NAC power or 10 A of general purpose
power.
• Four Class B (Style Y) or four Class A (Style Z) outputs,
individually addressable by the FACP.
• When built-in outputs are configured for NAC operation,
each circuit supports strobe synchronization with the follow-
ing manufacturers' audio/visual devices: System Sensor®
(SpectrAlert® and SpectrAlert Advance Series) or Whee-
lock or Gentex.
• Each circuit can be software-selected for use as: a Notifica-
tion Appliance Circuit, general purpose 24 VDC power, four-
wire detector power, or door holder.
• Steady, March Time (120 PPM), Two Stage, Temporal, or
UZC Zone-Coded and Non-Coded devices - software-
selectable by circuit.
• Universal Zone Coder (UZC-256) option supports for pro-
grammable coded outputs. Up to 256 different codes.
• Auxiliary Outputs: 24V @ 0.5A and 5V @ 0.15A.
• Charges 12 to 200 AH batteries with full supervision. The
charger on the ACPS may be disabled via software. When
disabled, a separate, external charger is required, for exam-
ple a CHG-120.
• May be used to provide battery backup for multiple ACPS
supplies.
• AC loss detection, brownout detection, and AC loss delay
reporting.
• Power-limited outputs.
• Isolated Signaling Line Circuit (SLC) interface.
• Selectable ground fault detection.
• Canadian two stage operation.
Specifications
• Primary (AC) power:
– ACPS-610: 120 VAC, 50/60 Hz input, 5.0 A maximum.
– ACPS-610E: 220/240 VAC, 50/60 Hz input, 2.5 A maxi-
mum.
• Output voltage: 24 VDC electrically regulated and power
limited (under primary AC mains). Under secondary power,
20.4 to 26.4 VDC.
• Output circuits - TB3, TB4, TB5, TB6 on Main Board: 1.5 A
maximum for any NAC output circuit. 2.5 A maximum for
any Power output with battery charger disabled.
• Secondary power (battery) charging circuit - lead-acid bat-
tery charger which will charge 12 to 200 AH batteries. Max-
imum charger current - 5.0 A.
• Secondary power auxiliary outputs - TB2 on CPS-24 Board:
– 24V @ 0.5A, power limited.
– 5V @ 0.15A, power limited.
• Wiring: utilizes wire sizes 12 to 18 AWG (3.1 to 0.78 mm²).
• SLC specifications: Average SLC current is 1.287 mA. SLC
data is transmitted between 24.0 VDC, 5 VDC, and 0 VDC
at approximately 3.33 Kbaud.
• Battery fuse (F2): 15A, Fast-acting.
• Weight: 4.5 lb.
ACPS Programming
The ACPS-610(E) is programmable via the simple-to-use
PK-PPS programming utility, which requires a Windows® PC
with a USB port and cable. Programming may be performed
during an on-line session with the ACPS-610(E), or previously
saved programs may be downloaded to individual ACPS-
610(E) units. The ACPS-610(E) requires the use of a minimum
of 5 SLC address points, and will use up to 14 SLC address
points to fulfill requirements for Canadian supervision and two
stage operation.