Notifier ONYX FirstVisio User Manual
Onyx firstvision, Interactive firefighters’ display, General
DN-7051:E2 • 5/15/2014 — Page 1 of 4
ONYX FirstVision™
Interactive Firefighters’ Display
Network Systems
DN-7051:E2 • A0-185
70
51c
o
v
-10.J
P
G
General
ONYX FirstVision™ is a revolutionary wayfinding navigational
tool for firefighters and other emergency responders. ONYX
FirstVision, a touch screen based annunciator, graphically dis-
plays critical information on the origin and spread of a fire;
allowing firefighters to quickly locate and extinguish the fire.
With ONYX FirstVision, emergency responders can immedi-
ately gather the information needed to accurately pinpoint the
source of the fire and the rate at which it’s spreading. Crucial
information is easy to access with a spatial, graphical depiction
of the location of activated detectors and detector sequence of
activation for one or multiple buildings. In addition, ONYX First-
Vision is an interactive interface. It displays a summary of
building floor plans with detailed information about the build-
ing. Details can include locations for all fire alarm devices;
water supplies; evacuation routes; access routes; chemical
and structural hazards in the building; and shutoffs for gas,
power, and HVAC.
Features
GENERAL
•
22" LCD touch-screen.
•
Interfaces with ONYX® Series panels or NOTI•FIRE•NET
(version 5.0 or higher) through the NFN Gateway over
Ethernet.
•
Compatible with standard and High Speed
NOTI•FIRE•NET™.
•
Supports the following additional languages: French (Cana-
dian), Hebrew, Korean, Portuguese, Spanish, Thai, and
Chinese (Traditional and Simplified).
•
Supports multiple gateways for large networks and cam-
puses.
USER INTERFACE
•
Large intuitive display shows building floor plans in a cam-
pus footprint with respective active fire alarm devices, water
supplies, evacuation routes, access routes, gas, power and
HVAC shutoffs, and chemical and structural hazards in the
building.
•
Detailed information for active devices or critical building
icons on the floor plan.
•
Easy access to building, emergency contacts, site plan, and
alarm event information.
•
Able to print screenshots.
•
Stores MSDS (Materials Safety Data Sheet) attachment.
•
User download of event log file.
EVENT NOTIFICATION
•
Graphic and text event notification of fire, supervisory, secu-
rity, and medical events.
•
Fast automatic navigation to floors and locations of the
emergency events.
•
Priority based event list display.
•
First alarm display to identify where the emergency started.
•
Time sequence display of activated detectors to track
smoke progression.
•
Configurable sound notification with silence selection.
•
Configurable to unlock door based on events.
SYSTEM SETUP
•
Screen development tool can easily import building floor
plan CAD drawings (as a .wmf, .bmp, or .jpg file) and Veri-
Fire® Tools databases.
•
Standard icon library indicates fire alarm and critical build-
ing devices.
•
Ethernet and USB ports available for transferring screen
database information.
Specifications
NOTE: Dimensions are subject to change. Contact NOTIFIER for
further information.
Enclosure Dimensions: 24.53" W X 21.92" H X 3.47" D
(62.30 cm H x 55.68 cm W x 8.81 cm D).
•
Door Dimensions: 26.70" W X 23.06" H X 0.41" D
(67.81 cm H x 58.57 cm W x .10 cm D).
•
Power Requirements: Regulated, filtered 24 VDC @ 3.0 A
via non-resettable power supply, UL/ULC Listed for fire-pro-
tective signaling use.
•
Temperature Range: 0°C – 50°C (32°F – 120°F).
Listings and Approvals
These listings and approvals apply to ONYX FirstVision™.
•
UL/ULC Listed: S5697
•
MEA: 286-07-E
•
CSFM: 7300-1525:0103
•
FDNY: COA#6070