Tone selection, Chime patterns – Notifier CHW Chimes User Manual
Page 3

Canadian DN-60029:A • 2/21/07 — Page 3 of 4
Tone Selection
Chime tone selection is accomplished by using the rotary switch on the back
of the product. The current draw and sound measurements for various
chime tones are listed below.
Chime Current Draw,
ULC Maximum (mA RMS)
Sound Output (dBA), Chime and Chime/Strobe
SpectrAlert Advance Chime/Strobe Dimensions
Sound Pattern
dB
8 – 17.5 Volts
16 – 33 Volts
DC
(mA)
FWR
(mA)
DC
(mA)
FWR
(mA)
1-Second Chime
HIGH
34
50
58
51
1-Second Chime
LOW
30
51
51
54
1/4-Second Chime
HIGH
34
51
50
50
1/4-Second Chime
LOW
31
51
50
52
Temporal Chime
HIGH
30
50
48
54
Temporal Chime
LOW
30
47
50
51
5-Second Whoop
HIGH
32
52
34
54
5-Second Whoop
LOW
30
40
34
52
One Test Chime
HIGH
48
49
50
50
Switch
Setting
Sound Pattern
dB
8 – 17.5 Volts
16 – 33 Volts
DC
(dBA)
FWR
(dBA)
DC
(dBA)
FWR
(dBA)
1
1-Second Chime
HIGH
82
85
85
85
2
1-Second Chime
LOW
76
79
77
77
3
1/4-Second Chime
HIGH
82
84
84
85
4
1/4-Second Chime
LOW
76
78
78
78
5
Temporal Chime
HIGH
85
90
90
93
6
Temporal Chime
LOW
79
80
80
80
7
5-Second Whoop
HIGH
87
93
92
97
8
5-Second Whoop
LOW
80
83
83
83
9
One Test Chime
HIGH
82
84
84
86
Chime Patterns
Setting
Repetition Rate
dB Out
1
1-Second Chime
HIGH
2
1-Second Chime
LOW
3
1/4-Second Chime
HIGH
4
1/4-Second Chime
LOW
5
Temporal Chime
HIGH
6
Temporal Chime
LOW
7
5-Second Whoop
HIGH
8
5-Second Whoop
LOW
9
One Test Chime
HIGH
7089dim1.tif