Page 2 of 4 — dn-2225:a1 • 2/9/10

GENERAL NOTES:

• Strobes are designed to flash at 1 flash per second minimum

over their “Regulated Voltage Range”. Note that NFPA-72

specifies a flash rate of 1 to 2 flashes per second and ADA

Guidelines specify a flash rate of 1 to 3 flashes per second.

• All candela ratings represent minimum effective Strobe inten-

sity based on UL Standard 1971.

• Series ET Speaker Strobes and Series ET Speakers are

listed under UL Standard 1971 for indoor use with a tempera-

ture range of 32°F to 120°F (0°C to 49°C) and maximum

humidity of 85%.

• Wheelock Weatherproof Appliances are designed to operate

over an extended temperature of -40° F to 150°F (-40°C to

66°C) and all candela ratings represent minimum effective

strobe intensity based on UL 1638. Maximum humidity of

93% RH + 2%.

• “Regulated Voltage Range” is the newest terminology used

by UL to identify the voltage range. Prior to this change UL

used the terminology “Listed Voltage Range”.

ARCHITECTURAL/ENGINEERING
SPECIFICATIONS

The speaker appliances shall be Wheelock Series ET Speakers

and speaker strobe appliances shall be Wheelock Series ET

Speaker Strobes or approved equals. The speakers shall be UL

Listed under Standard 1480 for Fire Protective Service and

speakers equipped with strobes shall be listed under UL Stan-

dard 1971 for Signaling Devices for the Hearing-Impaired. In

addition, the strobes shall be certified to meet the requirements

of FCC Part 15, Class B.
All speakers shall be designed for a field selectable input of

either 25 or 70 VRMS, with selectable power taps from 1/8 watt

to 8 watts. All models shall have listed sound output of up to 93

dB at 10 feet and a listed frequency response of 400 to 4000 Hz.

The speaker shall also incorporate a sealed back construction.

All inputs shall employ terminals that accept #12 to #18 AWG

wire sizes.
The strobe portion of the appliance shall produce a flash rate of

one (1) flash per second over the Regulated Voltage Range and

shall incorporate a Xenon flashtube enclosed in a rugged

Lexan® lens. The strobe shall be of low current design. Where,

Multi-Candela Speaker Strobes are specified, the strobe inten-

sity shall have field selectable settings and shall be rated per UL

Standard 1971 at 15/30/75/110cd or 135/185cd for wall mount

and 15/30/75/95 cd or 115/177cd for ceiling mount. The selector

switch for selecting the candela shall be tamper resistant. The

1575 strobe shall be specified when 15 candela UL Standard

1971 listing with 75 candela on-axis is required (e.g. ADA com-

pliance).
When synchronization is required, the strobe portion of the

appliance shall be compatible with Wheelock’s SM, DSM sync

modules or a a power supply with built-in Wheelock Patented

Sync Protocol. The strobes shall not drift out of synchronization

at any time during operation. If the sync module or Power Sup-

ply fails to operate, (i.e., contacts remain closed), the strobe

shall revert to a non-synchronized flash rate.
The speaker and speaker strobe appliances shall be designed

for indoor surface or flush mounting. The speaker and speaker

strobe shall incorporate a speaker mounting plate with a grille

cover which is secured with two screws for a level, aesthetic fin-

ish and shall mount to standard electrical hardware requiring no

additional trimplate or adapter. The finish of the Series ET

speakers and speaker strobes shall be white, red or nickel plate.

All speakers and speaker strobes shall be backward compatible.

!

WARNING: CONTACT WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS (P83983) SERIES
NS-24MCW, (P84234) SERIES NS-12 AND 24 VDC SINGLE CANDELA MODELS, (P83600) SERIES NH AND
“GENERAL INFORMATION” SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS UNDERGO
PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THE PRODUCTS.
THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO
SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING:

• TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY

POWER SOURCES.

• FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM

ALL APPLIANCES ON THOSE CIRCUITS.

• COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON’S FIELD OF VIEW.
• ADDING, REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELLA SETTINGS WILL

AFFECT CURRENT DRAW. RECALCULATE CURRENT DRAW TO INSURE THAT THE TOTAL
AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE
RATED CAPACITY OF THE POWER SOURCES OR FUSES.

• THE VOLTAGE APPLIED TO THE PRODUCTS MUST BE WITHIN THEIR “REGULATED VOLTAGE

RANGE.”

• INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS.
• INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES.
• THESE APPLIANCES ARE NOT DESIGNED TO BE USED ON CODED SYSTEMS IN WHICH THE

APPLIED VOLTAGE IS CYCLED ON AND OFF.

• FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION

SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND/OR PROPERTY
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

• CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION

PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT
INSTALLATIONS.