Operating and installation instructions

CONA

®

S - Ball float steam traps

4.4 Technical data - remarks

for
- Principal dimensions,
- Pressure-temperature-ratings, operating limits,
- Valves with different types of connection , etc.

refer to datasheet.

4.5 Marking

Details of the CE-marking on the valve:

5.0 Installation

5.1 General notes on installation

The following points should be taken into account besides the general principles governing
installation work:

- Planners / construction companies or operators are responsible for positioning and

installing products.

CE-marking

0045 Notified body

Manufacturer

Address of manufacturer:
refer to item 11.0 Warranty / Guarantee

Typ

Type

Bj.

Year of manufacture

According to the Pressure Equipment Directive appendix 2 diagram 7 valves acc. to article
1 paragraph 2.1.2 (pipes) only show the CE-marking from DN40 onwards.

ATTENTION !
- Remove flange covers if present.
- The interior of valve and pipeline must be free from foreign particles.
- It is possible to install the float steam trap for vertical or horizontal flow. Note

installation position with reference to flow, see mark on valve.

- Steam and air line systems should be designed to prevent water accumulation.
- Lay pipelines so that damaging transverse, bending and torsional forces are

avoided.

- Protect valves from dirt during construction work.
- Connection flanges must mate precisely.
- Valves must not be used to take external forces, e.g. they are not designed for

use as climbing aids, or as connecting points for lifting gear.

- Suitable materials handling and lifting equipment should be used.

See data sheet for weights.

- Centre gaskets between the flanges.
- Precautions against freezing should be taken as a matter of course in any

facilities susceptible to frost. If a system not in operation is in a position
susceptible to freezing, we recommend that the drain plug (Pos. 50) on the
unpressurised steam trap be unscrewed, the residual condensate drained off,
the seal faces cleaned and the plug screwed down again.
The sealing ring (Pos. 49) should be replaced if necessary.
(see Fig. 1 - Fig. 2 page 4)