beautypg.com

3 tightening torques, 1 tightening torques for hexagon nuts (bonnet), 2 tightening torques for hexagon nuts (plug) – ARI Armaturen STEVI 451 EN User Manual

Page 19: 3 tightening torques for seat rings, 0 troubleshooting, Refer to item 7.3.), Rques refer to item 7.3.)

background image

Rev. 0040306000 0410

Page 19

Operating and installation instructions

3-way control valves - STEVI

®

450 / 451

7.3 Tightening torques

7.3.1 Tightening torques for hexagon nuts (bonnet)

7.3.2 Tightening torques for hexagon nuts (plug)

7.3.3 Tightening torques for seat rings

Refer to operating and installation instructions for actuator

concerned for installing actuators!

8.0 Troubleshooting

In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.

If malfunctions cannot be eliminate with the help of the following table
9.0 Troubleshooting table”, the supplier or manufacturer should be consulted.

(Pos. 11, 29, 20.8)
M 10

=

15 - 30 Nm

M 12

=

35 - 50 Nm

M 16

=

80 - 120 Nm

M 20

=

150 - 200 Nm

(Pos. 4)

(Pos. 60)

M 10

=

50 Nm

M 10

=

35 Nm

M 12

=

85 Nm

M 12

=

60 Nm

M 16

=

180 Nm

M 16

=

140 Nm

M 20 x 1,5

=

360 Nm

M 20 x 1,5

=

270 Nm

(Pos. 2)
DN 15

=

150 Nm

DN 20

=

200 Nm

DN 25

=

215 Nm

DN 32

=

280 Nm

DN 40

=

400 Nm

DN 50

=

550 Nm

DN 65

=

840 Nm

DN 80

=

1170 Nm

DN100

=

1680 Nm

DN125 / 125v

=

1700 Nm

DN150 / 150v

=

2000 Nm

-

ATTENTION !
- It is essential that the safety regulations are observed when identifying faults.

This manual is related to the following products: