Operating and installation instructions

3-way control valves - STEVI

®

450 / 451

7.2.2 Diverting plug design
DN40-150
- Slacken screw joint (pos. 19 and 24) by about 1

turn.

- Loose nuts (pos. 11).
- Detach mounting bonnet (pos. 7).
- Loose nut (pos. 4 or pos. 60).
- Pull plug (pos. 31) with distance bush (pos. 32)

down.

Note:
There is no distance bush (pos. 32) in DN125-150.
- Pull plug (pos. 40) with stem (pos. 41) up and

replace.

Note:
DN125-150: Bolt new parts together, drill and pin
them.
- Unscrew seat rings (pos. 2 bottom and top) and

renew or recondition.
(For tightening torques refer to item 7.3.)

- Replace gasket (pos. 9).
- Assemble in reverse order.

(For tightening torques refer to item 7.3.)

- Secure with nuts (pos. 11) and tighten them

crosswise.
(For tightening torques refer to item 7.3.)

(top)

(bottom)

Fig. 22:
Series 450 DN40-150 with diverting
plug Verteilkegel