Calibration procedures, 0 field calibration, Rtd temperature to resistance conversion table – Red Lion IRMA User Manual

Page 4

background image

4

Field Calibration with an Accurate Adjustable Resistance Source

Note: The nominal output value for the various output ranges are designated in the

following order: (0 to 20 mA, 4 to 20 mA, 0 to 10 VDC)

1.1 Connect resistance source to the RTD input terminals using a third sense wire.

(For 2 wire sensors, short terminal #7 to terminal #8.)

1.2 Set the type and Range for the RTD or resistance used in your application. (DIP

switches #4, #6, #7 & #8). (RTD alpha = 0.00385, Range 0 shown). APPLY
OPERATING VOLTAGE and allow 45 minute warm-up period.

1.3 Set the FIELD CAL switch (#2) ON. [Output goes to -0.8 mA, 3.5 mA, or -0.4 V

nominal]

1.4 Set the input resistance to the value intended to generate the analog low endpoint

(For 2 wire sensors, add the system lead resistance to the desired value.)

1.5 Set the OUTPUT CAL switch (#1) ON. [Output stays at -0.8 mA, 3.5 mA, or -0.4

V nominal]

1.6 Adjust the input signal up until the analog output equals desired low value.[0 mA,

4 mA, or 0 V]

1.7 Set the OUTPUT CAL switch (#1) OFF. [Output increases to 22.9 mA, 22.5 mA,

or 11.5 V nominal]

1.8 Set the input resistance to the value intended to generate the analog high endpoint.

(For 2 wire sensors, add the system lead resistance to the desired value.)

1.9 Set the OUTPUT CAL switch (#1) ON. [Output decreases to 21.1 mA, 20.7 mA,

or 10.6 V nominal]

1.10 Adjust the input signal down until the output equals desired high value. [20 mA,

20 mA, or 10 V]

1.11 Set the OUTPUT CAL switch (#1) OFF.

1.12 Set the FIELD CAL switch (#2) OFF.

1.13 Disconnect the resistance source from the IRMA and connect the actual sensor to

be used in the application.

DIP SWITCH SETTINGS:

ON = 1

OFF = 0

9-32 VDC

V+

I+

VDC+

RTD(S)

POWER

RTD(-)

RTD(+)

VDC-

9

ERROR

7

8

12

10

11

6

3

4

1

5

2

V-

I-

5

1

4
3
2

8
7
6

RANGE

RANGE

OHMS/RTD

FIELD CAL

BASIC CAL

OUTPUT CAL

392

SEN UP/DN

MODEL IRMA

ERROR

POWER

VDC+

10

RTD(S)

7

V+

4

I+

1

VDC-

RTD(+)

12

11

9

8

6

5

V-

3

2

I-

POWER SUPPLY

9 to 32 VDC

VOLTAGE METER

OR

CURRENT METER

MONITORING INSTRUMENT

RTD(-)

ADJUSTABLE
RESISTANCE

SOURCE

-

+

S

Field Calibration Wiring

1.0 Field Calibration

CALIBRATION PROCEDURES

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

1

6

5

4

3

2

8

7

ON

Step 1.11

Step 1.12

Step 1

.

2

Step 1.3

Step 1.5

Step 1.7

Step 1.9

Field Calibration scales the selected output to a temperature or resistance

input. This procedure assigns an input value to the low end and an input value
to the high end. The microprocessor handles configuring the output so it is
linear to the temperature or resistance input. The Field Calibration procedure is
described below.

Note: The unit needs to have the Field Calibration completed by the operator

before normal operation. To abort this calibration and reset to the previous
settings, set the FIELD CAL switch OFF prior to the final OFF setting of the
OUTPUT CAL switch (Step 1.11) and turn off power. Wait 5 seconds and then
turn on power and the previous settings will be loaded.

RTD temperature to resistance conversion table

195.80

194.09

250

177.23

175.85

200

173.48

172.17

190

158.36

157.33

150

139.20

138.5

100

119.75

119.40

50

100.00

100.00

0

79.96

80.30

-50

59.55

60.25

-100

38.64

39.71

-150

34.38

35.53

-160

alpha

0.00392

alpha

0.00385

Temperature

°C

333.90

329.54

650

330.68

326.38

640

317.66

313.63

600

314.38

310.41

590

301.13

297.42

550

284.30

280.92

500

267.18

264.13

450

253.28

250.49

410

249.77

247.05

400

232.07

229.69

350

214.08

212.03

300

alpha

0.00392

alpha

0.00385

Temperature

°C