Red Lion IAMA0006 User Manual
Cc us us, Listed, General description
1
3-WAY ISOLATION OF ANALOG SIGNALS
UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS
SELECTED VIA DIP SWITCH SETTINGS
OVER 35 INPUT AND OUTPUT ANALOG CONVERSION
COMBINATIONS
ULTRA SLIM DESIGN – ONLY 0.244" WIDE
19 to 30 VDC POWER
GENERAL DESCRIPTION
The IAMA can isolate and convert over 35 combinations of analog signal
ranges. The IAMA converts and transmits signals linearly proportional to the
input. DIP switch range selection eliminates the need to order and stock
different modules for each input and output signal range, and allows quick and
convenient setup for over 35 standard signal conversions. In addition to the
conversion capabilities, the IAMA modules feature optically isolated Input/
Output signal circuits and isolated Power to Input, Power to Output circuits. The
modules’ overall full scale accuracy typically exceed 0.04%. DIN rail mounting
saves time and panel space. The units are equipped with universal mounting feet
for attachment to standard top hat profile rail according to EN50022 - 35x7.5.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
1. POWER: 19.2 to 30 V DC, 450 mW max.
2. INPUT / OUTPUT RANGES: See table 1
3. SPAN ADJUSTMENT: Potentiometer, located below transparent top cover.
4. MAX INPUT SIGNAL:
Current: 50 mA
Voltage: 30 V
5. INPUT RESISTANCE:
Current: Approx. 50
Voltage: Approx. 100 k
6. OUTPUT: Self-powered (Active)
7. MAX OUTPUT SIGNAL:
Current: 28 mA/12.5 V
Voltage: 12.5 V/22 mA
8. LOAD RESISTANCE:
Current: 500
max.
Voltage: 10 k
min
9. OUTPUT COMPLIANCE:
Current: 12.5 V max (500
). Ripple: < 20 mV
Voltage: 22 mA (10 k
). Ripple: < 20 mV
10. TRANSMISSION ERROR:
The transmission error without adjustment is < 0.4%. Using the potentiometer,
the error can be adjusted to < 0.1%.
11. TEMPERATURE COEFFICIENT:
Max.: < 0.01%/K
Typ.: < 0.002%/K
12. CUT-OFF FREQUENCY: 100 Hz
13. STEP RESPONSE (FROM 10 to 90 %): 3.5 msec
14. TEST VOLTAGE (Input/Output/Supply): 1.5 kV, 50 Hz, 1 min.
15. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -20°C to 65°C (-4°F to 149°F)
Storage Temperature Range: -40°C to +85°C (-40°F to 185°F)
MODEL IAMA - CONFIGURABLE 3-WAY ISOLATING AMPLIFIER
Bulletin No. IAMA6-B
Drawing No. LP0609
Released 01/13
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
3.65 (92.7)
1
6
1 2
off
S1
on
S2
on
off
4.00
4
3
1
2
0.24
(6.2)
(101.6)
1
8
7
6
5
4
3
2
DIMENSIONS In inches (mm)
MODEL NO.
DESCRIPTION
PART NUMBER
IAMA
IAMA0006
Configurable 3-Way Isolating Amplifier
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
ORDERING INFORMATION
CC
US
US
UL
R
LISTED
PROCESS CONTROL
EQUIPMENT FOR HAZARDOUS
LOCATIONS 31ZN
CLASS 1, DIV 2
GROUPS A, B, C, D T5