GENERAL SPECIFICATIONS

1. POWER: Derived from system backplane. (75 mA load on power input of

MASTER). Module may be hot-swapped (replaced while powered up).

2. LEDs:

STS - Status LED shows module condition.
ALM - Alarm LED is lit during any internal alarm condition.

3. MEMORY: Non-volatile memory retains all programmable parameters.

MASTER also stores the parameters in order to reprogram modules that are
replaced.

4. ISOLATION LEVEL: 500 Vrms @ 50/60 Hz for 1 minute between the

Signal Inputs and the CS Master Power Supply Input.

5. COMMUNICATIONS: Provided by the CS Master
6. CERTIFICATIONS AND COMPLIANCES:

SAFETY
Check each module’s specifications to determine system compliance.
UL Listed, File #E302106, UL508, CSA 22.2 No. 14-M05 and File #E179259,

UL61010-1, CAN/CSA-C22.2 No. 61010-1; and File #E317425, ANSI/ISA
12.12.01-2007, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment

for measurement, control, and laboratory use, Part 1.

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: 2006: Electrical Equipment for
Measurement, Control and Laboratory use.

Immunity to Industrial Locations:
Electrostatic discharge

EN 61000-4-2 Criterion B

4kV contact discharge
8kV air discharge

Electromagnetic RF fields

EN 61000-4-3 Criterion B

3

10V/m (80 MHz to 1 GHz)
3 V/m (1.4 GHz to 2 GHz)
1 V/m (2 GHz to 2.7 GHz)

Fast transients (burst)

EN 61000-4-4 Criterion B

power 2kV

I/O signal 1kV

Surge

EN 61000-4-5 Criterion B

power 1 kV L to L, 2 kV L to G

signal 1 kV

RF conducted interference

EN 61000-4-6 Criterion A

3 Vrms

Emissions:
Emissions

EN55011

Class A

Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self-

recovers.

3. The module’s analog input and/or output signals may deviate during

disturbance, but self-recover when disturbance is removed.

4. Power supplied from backplane via Master Module.

7. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to +50 °C
Storage Temperature Range: -40 to +85 °C
Operating and Storage Humidity: 85% max relative humidity, non-

condensing, from 0 to +50 °C

Vibration According to IEC 68-2-6: Operational 10 to 150 Hz, 0.075 mm

amplitude in X, Y, Z direction 1 g.

Shock According to IEC 68-2-27: Operational 25 g, 11 msec in 3 directions.
Altitude: Up to 2000 meters

8. CONSTRUCTION: Case body is burgundy high impact plastic. For indoor

use only. Installation Category II, Pollution Degree 2.

9. CONNECTIONS: Removable wire clamp screw terminal blocks

Wire Gage: 28-16 AWG terminal gage wire
Torque: 1.96-2.23 inch/lbs (0.22-0.25 N-m)

10. MOUNTING: Snaps on to standard DIN style top hat (T) profile mounting

rails according to EN50022 -35 x 7.5 and -35 x 15.

11. WEIGHT: 6 oz (170.1 g)

CSTC8 SPECIFICATIONS

12. INPUTS:

Channels: 8 single-ended
Effective Resolution: Full 16-bit
Sample Time: 50 msec - 400 msec, depending on number of enabled inputs.

ENABLED

INPUTS

SCAN TIME

(READING RATE)

1

50 msec (20 Hz)

2

100 msec (10 Hz)

3

150 msec (6.7 Hz)

4

200 msec (5 Hz)

5

250 msec (4 Hz)

6

300 msec (3.3 Hz)

7

350 msec (2.9 Hz)

8

400 msec (2.5 Hz)

Common Mode Rejection: >110 dB, 50/60 Hz
Normal Mode Rejection: >90 dB, 50/60 Hz
Temperature Coefficient: 0.01%/°C
Step Response Time: One scan time (to within 99% of final value)
Types: T, E, J, K, R, S, B, N, C
Slope & Offset: Provides sensor error correction
Input Impedance: 20 M

Lead Resistance Effect: 0.25 μV/

Cold Junction Compensation: Less than ±1 °C typical (±1.5 °C max) over 0

to 50 °C ambient temperature

Resolution: 0.1°

13. TEMPERATURE INDICATION ACCURACY: ± (0.3% of span, +1 °C).

Includes NIST conformity, cold junction effect, A/D conversion errors,
temperature coefficient and linearization conformity at 23 °C after 20 minute
warm up.

14. PROBE BREAK RESPONSE: Upscale drive, Input Fault Alarm bit set high,

ALM LED illuminates.

No Standard

No Standard

No Standard

No Standard

-10.00 to +56.00 mV

0 to +2315 °C

+32 to +4199 °F

Millivolt

C

W5/W6

(+) Orange

(-) Blue

(+) Orange

(-) Red

-200 to +1300 °C

-328 to +2372 °F

N

No Standard

No Standard

+149 to +1820 °C

+300 to +3308 °F

B

(+) White

(-) Blue

No Standard

0 to +1768 °C

+32 to +3214 °F

S

(+) White

(-) Blue

No Standard

0 to +1768 °C

+32 to +3214 °F

R

(+) Brown

(-) Blue

(+) Yellow

(-) Red

-200 to +1350 °C

-328 to +2462 °F

K

(+) Yellow

(-) Blue

(+) White

(-) Red

-200 to +760 °C

-328 to +1400 °F

J

(+) Brown

(-) Blue

(+) Violet

(-) Red

-200 to +730 °C

-328 to +1346 °F

E

(+) White

(-) Blue

(+) Blue

(-) Red

-200 to +400 °C

-328 to +752 °F

T

BS 1843

ANSI

WIRE COLOR

MEASUREMENT

RANGE

TYPE

2

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR
AREA IS KNOWN TO BE NON-HAZARDOUS.

This manual is related to the following products: