General specifications, Cstc8 specifications – Red Lion CSRTD6 User Manual
Page 2

GENERAL SPECIFICATIONS
1. POWER: Derived from system backplane. (75 mA load on power input of
MASTER). Module may be hot-swapped (replaced while powered up).
2. LEDs:
STS - Status LED shows module condition.
ALM - Alarm LED is lit during any internal alarm condition.
3. MEMORY: Non-volatile memory retains all programmable parameters.
MASTER also stores the parameters in order to reprogram modules that are
replaced.
4. ISOLATION LEVEL: 500 Vrms @ 50/60 Hz for 1 minute between the
Signal Inputs and the CS Master Power Supply Input.
5. COMMUNICATIONS: Provided by the CS Master
6. CERTIFICATIONS AND COMPLIANCES:
SAFETY
Check each module’s specifications to determine system compliance.
UL Listed, File #E302106, UL508, CSA 22.2 No. 14-M05 and File #E179259,
UL61010-1, CAN/CSA-C22.2 No. 61010-1; and File #E317425, ANSI/ISA
12.12.01-2007, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: 2006: Electrical Equipment for
Measurement, Control and Laboratory use.
Immunity to Industrial Locations:
Electrostatic discharge
EN 61000-4-2 Criterion B
4kV contact discharge
8kV air discharge
Electromagnetic RF fields
EN 61000-4-3 Criterion B
3
10V/m (80 MHz to 1 GHz)
3 V/m (1.4 GHz to 2 GHz)
1 V/m (2 GHz to 2.7 GHz)
Fast transients (burst)
EN 61000-4-4 Criterion B
power 2kV
I/O signal 1kV
Surge
EN 61000-4-5 Criterion B
power 1 kV L to L, 2 kV L to G
signal 1 kV
RF conducted interference
EN 61000-4-6 Criterion A
3 Vrms
Emissions:
Emissions
EN55011
Class A
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self-
recovers.
3. The module’s analog input and/or output signals may deviate during
disturbance, but self-recover when disturbance is removed.
4. Power supplied from backplane via Master Module.
7. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to +50 °C
Storage Temperature Range: -40 to +85 °C
Operating and Storage Humidity: 85% max relative humidity, non-
condensing, from 0 to +50 °C
Vibration According to IEC 68-2-6: Operational 10 to 150 Hz, 0.075 mm
amplitude in X, Y, Z direction 1 g.
Shock According to IEC 68-2-27: Operational 25 g, 11 msec in 3 directions.
Altitude: Up to 2000 meters
8. CONSTRUCTION: Case body is burgundy high impact plastic. For indoor
use only. Installation Category II, Pollution Degree 2.
9. CONNECTIONS: Removable wire clamp screw terminal blocks
Wire Gage: 28-16 AWG terminal gage wire
Torque: 1.96-2.23 inch/lbs (0.22-0.25 N-m)
10. MOUNTING: Snaps on to standard DIN style top hat (T) profile mounting
rails according to EN50022 -35 x 7.5 and -35 x 15.
11. WEIGHT: 6 oz (170.1 g)
CSTC8 SPECIFICATIONS
12. INPUTS:
Channels: 8 single-ended
Effective Resolution: Full 16-bit
Sample Time: 50 msec - 400 msec, depending on number of enabled inputs.
ENABLED
INPUTS
SCAN TIME
(READING RATE)
1
50 msec (20 Hz)
2
100 msec (10 Hz)
3
150 msec (6.7 Hz)
4
200 msec (5 Hz)
5
250 msec (4 Hz)
6
300 msec (3.3 Hz)
7
350 msec (2.9 Hz)
8
400 msec (2.5 Hz)
Common Mode Rejection: >110 dB, 50/60 Hz
Normal Mode Rejection: >90 dB, 50/60 Hz
Temperature Coefficient: 0.01%/°C
Step Response Time: One scan time (to within 99% of final value)
Types: T, E, J, K, R, S, B, N, C
Slope & Offset: Provides sensor error correction
Input Impedance: 20 M
Lead Resistance Effect: 0.25 μV/
Cold Junction Compensation: Less than ±1 °C typical (±1.5 °C max) over 0
to 50 °C ambient temperature
Resolution: 0.1°
13. TEMPERATURE INDICATION ACCURACY: ± (0.3% of span, +1 °C).
Includes NIST conformity, cold junction effect, A/D conversion errors,
temperature coefficient and linearization conformity at 23 °C after 20 minute
warm up.
14. PROBE BREAK RESPONSE: Upscale drive, Input Fault Alarm bit set high,
ALM LED illuminates.
No Standard
No Standard
No Standard
No Standard
-10.00 to +56.00 mV
0 to +2315 °C
+32 to +4199 °F
Millivolt
C
W5/W6
(+) Orange
(-) Blue
(+) Orange
(-) Red
-200 to +1300 °C
-328 to +2372 °F
N
No Standard
No Standard
+149 to +1820 °C
+300 to +3308 °F
B
(+) White
(-) Blue
No Standard
0 to +1768 °C
+32 to +3214 °F
S
(+) White
(-) Blue
No Standard
0 to +1768 °C
+32 to +3214 °F
R
(+) Brown
(-) Blue
(+) Yellow
(-) Red
-200 to +1350 °C
-328 to +2462 °F
K
(+) Yellow
(-) Blue
(+) White
(-) Red
-200 to +760 °C
-328 to +1400 °F
J
(+) Brown
(-) Blue
(+) Violet
(-) Red
-200 to +730 °C
-328 to +1346 °F
E
(+) White
(-) Blue
(+) Blue
(-) Red
-200 to +400 °C
-328 to +752 °F
T
BS 1843
ANSI
WIRE COLOR
MEASUREMENT
RANGE
TYPE
2
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR
AREA IS KNOWN TO BE NON-HAZARDOUS.