Adding Option Cards
The PAX and MPAX series meters can be fitted with up to three optional plug-
in cards. The details for each plug-in card can be reviewed in the specification
section of the PAX Bulletin. Only one card from each function type can be
installed at one time. The function types include Setpoint Alarms (PAXCDS),
Communications (PAXCDC), and Analog Output (PAXCDL). The plug-in cards
can be installed initially or at a later date.
SETPOINT ALARMS PLUG-IN CARDS (PAXCDS)
The PAX and MPAX series has 4 available setpoint alarm output plug-in
cards. Only one of these cards can be installed at a time. (Logic state of the
outputs can be reversed in the programming.) These plug-in cards include:
PAXCDS10 - Dual Relay, FORM-C, Normally open & closed
PAXCDS20 - Quad Relay, FORM-A, Normally open only
PAXCDS30 - Isolated quad sinking NPN open collector
PAXCDS40 - Isolated quad sourcing PNP open collector
ANALOG OUTPUT PLUG-IN CARD (PAXCDL)
Either a 0(4)-20 mA or 0-10 V retransmitted linear DC output is available
from the analog output plug-in card. The programmable output low and high
scaling can be based on various display values. Reverse slopes output is possible
by reversing the scaling point positions.
PAXCDL10 - Retransmitted Analog Output Card
COMMUNICATION PLUG-IN CARDS (PAXCDC)
A variety of communication protocols are available for the PAX and MPAX
series. Only one of these cards can be installed at a time. When programming the
unit via Crimson (for MPAXI) or SFPAX (for MPAXCK or MPAXTM), the
RS232 or RS485 Cards must be used.
MPAXI/C/R Note: For Modbus communications, use RS485 Communications
Output Card and configure Communication Type parameter (tYPE) for Modbus.
PAXCDC10 - RS485 Serial (Terminal) PAXCDC1C - RS485 Serial (Connector)
PAXCDC20 - RS232 Serial (Terminal) PAXCDC2C - RS232 Serial (Connector)
PAXCDC30 - DeviceNet
* PAXCDC40 - Modbus (Terminal)
* PAXCDC4C - Modbus (Connector)
PAXCDC50 - Profibus-DP
* MPAXCK/MPAXTM only.
PROGRAMMING SOFTWARE
CRIMSON - MPAXI Only
Crimson is a Windows
®
based program that allows configuration of the
EPAX meter from a PC. Crimson offers standard drop-down menu commands,
that make it easy to program the EPAX meter. The EPAX program can then be
saved in a PC file for future use. A PAX serial plug-in card is required to
program the meter using the software.
SFPAX - MPAXCK and MPAXTM Only
The SFPAX is a Windows
®
based program that allows configuration of the
EPAX meter from a PC. Using the SFPAX makes it easier to program the EPAX
meter and allows saving the PAX program in a PC file for future use. On-line
help is available within the software. A PAX serial plug-in card is required to
program the meter using the software.
6. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010A-1, CSA C22.2
No. 1010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Indoor Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/8843/UL
CB Scheme Test Report #04ME11209-20041018
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
EMC specifications determined by the MPAX module.
7. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: Determined by the MPAX module
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. RH (non-condensing)
Altitude: Up to 2000 meters
8. MOUNTING REQUIREMENTS:
Max. panel thickness is 0.375" (9.5 mm)
Min. panel thickness for NEMA 4/IP65 sealing is 0.060" (1.52 mm)
9. MODULE INSTALLATION:
24-pin shrouded connector on EPAX engages connector on MPAX module
upon installation. Shroud ensures proper alignment by providing a lead-in for
the module connector.
10. CONNECTIONS: Wiring connections are made to the EPAX terminal
block and MPAX module via high compression cage-clamp terminal blocks.
MPAX Module Wiring: Instructions are provided in the corresponding PAX
Bulletin.
EPAX Terminal Block Wiring:
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-12 AWG copper wire
Maximum Torque: 5-7 inch-lbs (0.58-0.81 N-m)
CAUTION: DISCONNECT ALL POWER BEFORE
INSTALLING OR REMOVING MODULE
11. CONSTRUCTION: Aluminum front panel, enclosure, and rear cover with
textured black polyurethane paint for scratch and corrosion resistance
protection. Sealed front panel meets NEMA 4X/IP65 specifications for
indoor use when properly installed. Installation Category II, Pollution Degree
2. Panel gasket and keps nuts included.
12. WEIGHT: 5 lbs (2.25 kg) (less module)
* For detailed module and plug-in card specifications,
see corresponding PAX literature. (i.e. For MPAXI
specifications, see the PAXI literature)
OPTIONAL PLUG-IN CARDS AND ACCESSORIES
About the MPAX Input Modules
The MPAX Module serves as the input to the EPAX Display. There are several different modules to cover a variety of inputs. The MPAX module provides input
scaling which allows the EPAX to display most any engineering unit. Once the MPAX is inserted into the EPAX, the unit has the same functions and capabilities of
our PAX Series Intelligent Panel Meters. A full set of PAX programming instructions will be included with the MPAX module.
Selecting Your Display Components and Option Cards
To build a complete display unit, you will need an EPAX and an MPAX Input Module. The EPAX is only a display and will not operate without an MPAX module.
Please use the following chart to identify the appropriate MPAX module and EPAX Display that will satisfy your application.
OPTIONAL PLUG-IN CARD COMPATABILITY
-
YES
-
-
-
REAL-TIME
CLOCK
-
-
-
-
YES
ANALOG
YES
YES
EPAX0600
EPAX0600
MPAXTM00
MPAXCK00
-
Timer
Real-Time Clock/Timer
EPAX0600
MPAXR020
-
Rate
EPAX0600
MPAXC020
YES
Count
EPAX0600
MPAXI020
COMMS
Count/Rate/Serial Slave
EPAX
DISPLAYS
85-250 VAC
YES
YES
SIGNAL TYPE
YES
YES
MPAX MODULES
*
YES
SETPOINT