Chapter 4 _______________________________________________________Serial Communication

VAISALA _______________________________________________________________________ 21

Setting Relay Trigger Points

The relays of the transmitter turn

ON

/

OFF

when the CO

2

content reaches

the predefined trigger point. For the

ON

/

OFF

selection, see section Relays

on page 17.

There are two trigger points for both relays. The higher limit

activates the relay and the lower deactivates it. The two limits are used to
prevent the relay switching back and forth when the measured value is
very close to set point.

Both commands can also be entered without entering a trigger point
value. The command without parameters gives the current set value.

MF_Rx_HIGH yyy

where:
x = 1 or 2 (number of the relay)
yyy = trigger point (CO

2

content in ppm)

Example of setting the higher trigger limit of the relay 1:

>MF_R1_HIGH 1200
MF_R1_HIGH=1200.0000
>

Save the settings:

MAIN_SAVE F

Give the lower trigger limit:

MF_Rx_LOW yyy

where:
x= 1 or 2 (number of the relay)
yyy = trigger point (CO

2

content in ppm)

Example of setting the lower trigger limit of the relay 1:

>MF_R1_Low 900
MF_R1_LOW=900.000000
>

Save the settings:

MAIN_SAVE F