Servicing should only be performed by a Qualified Service Technician

TROUBLESHOOTING

COMPLAINT

CAUSE

REMEDY

USER

QUALIFIED AGENCY

*Water not hot enough.

Thermostat set too low.

Set thermostat dial to a

higher temperature

Upper and/or lower

temperature probe out of

calibration.

Call qualified agency.

Check continuity and resistance

(Ohms) of upper and lower

temperature probes. Replace

probes if out of specification.

*Insufficient hot water.
*See WATER TEMPERATURE

CONTROL WARNING on page

12 of Instruction Manual.

Thermostat set too low.

Set thermostat dial to a

higher temperature

Upper and/or lower

temperature probe out of

calibration.

Call qualified agency.

Check continuity and resistance

(Ohms) of upper and lower

temperature probes. Replace

probes if out of specification.

Main manual gas shutoff

valve partially closed.

Open main manual gas

shutoff valve to fullest extent.

Heater too small for demand. Space usage to give heater

time to restore water

temperature.

Heater recovery is slower.

Call qualified agency.

Check gas input. If incorrect, check

for inlet air blockage and/or flue

gas exhaust blockage.

Water temperature too hot.

Thermostat set too high.

Set thermostat to a lower

setting.

Rumbling.

Sediment accumulation on

bottom of tank.

Drain a quantity of water

through drain valve. If

rumbling persists, call

qualified agency.

Delime heater.

Ticking or metallic sounds.

Expansion and contraction -

normal.

Pounding or water hammer.

Air chambers in piping

have become waterlogged.

Thermal expansion tank

damaged, improperly

charged, or improperly sized.

Drain piping system and

refill. Heater must be off

while this is being done.

Check thermal expansion

tank charge pressure when

the water system pressure

is zero.

Follow the manufacturer's

instructions for proper charging of

the thermal expansion tank.

Water leaks.

Drain valve not closed tightly. If drain valve cannot be

closed tightly, replace.

If leakage source cannot be

corrected or identified, call

qualified agency.

Shut off gas supply to heater

and close cold water inlet

valve to heater.

Repair or in case of suspected

tank leakage, be certain to confirm

before replacing heater.

Gas odors.

Possible gas leaks.

Shut off gas supply to heater

and call gas company at

once.