Lime accumulation not only reduces the life of the equipment but

also reduces efficiency of the heater and increases fuel consumption.

The usage of water softening equipment greatly reduces the

hardness of the water. However, this equipment does not always

remove all of the hardness (lime). For this reason it is recommended

that a regular schedule for deliming be maintained.
The time between cleaning will vary from weeks to months depending

upon water conditions and usage.
The depth of lime buildup should be measured periodically. Heaters

equipped with cleanouts will have about 2” of lime buildup when

the level of lime has reached the bottom of the cleanout opening. A

schedule for deliming should then be set up,based on the amount

of time it would take for a 1” buildup of lime. It is recommended that

the water heater initially be inspected after 6 months.
Example 1:

Initial inspection after 6 months shows 1/2” of lime accumulation.

Therefore, the heater should be delimed once a year.

Example 2:

Initial inspection after 6 months shows 2” of lime accumulation.

Therefore, the heater should be delimed every 3 months.

fIGure 21.

delIMInG solvents

UN•LIME is recommended for deliming. UN•LIME is a patented

food grade acid which is safe to handle and does not create the

harmful fumes which are associated with other products.
UN•LIME may be obtained from your dealer, distributor or water

heater manufacturer. Order Part Number 9005416105, 1 gallon,

packed 4 gallons per case or Part Number 9005417105, 5

gallon container.
note: Un•Lime is not available for use in Canada.
Hydrochloric base acids are not recommended for use on glass

lined tanks.
Observe handling instructions on label of product being used.

tanK cleanout procedure

The following practices will ensure longer life and enable the unit to

operate at its designed efficiency:
1. Once a month the heater should be flushed. Open the drain valve

and allow two gallons of water to drain from the heater. Inlet water

valve should remain open to maintain pressure in tank.

2. A cleanout opening is provided for periodic cleaning of the tank.

Gas must be shut off and heater drained before opening cleanout.

To clean heater through cleanout opening, proceed as follows:

1. Drain heater.
2. Remove outer cover plate from lower side of heater jacket.
3. Remove six (6) hex head screws securing tank cleanout plate

and remove plate.

4. Remove lime, scale, or sediment using care not to damage the

glass lining.

5. Inspect cleanout plate gasket, if new gasket is required, see

replacement parts list for item number.

6. Install cleanout plate. Be sure to draw plate up tight by tightening

screws securely.

7. Replace outer jacket cover plate.

fIGure 22.

9. In some water areas the sediment might not be removed

by this method and may result in the water heater making

rumbling or boiling noises. To dissolve and remove these more

stubborn mineral deposits, UN•LIME Professional Delimer

should be used.

delIMInG usInG flo-juG Method

UN•LIME in the 5 gallon size is recommended for deliming of the

BT-75 and 100 models. UN•LIME with the necessary hoses and

fittings to delime your heater is also available as a kit: Up-N-Down

Transfer Kit. Contact your local dealer, distributor or water heater

manufacturer.

prepare the water heater

To delime the water heater using the Flo-Jug method, first prepare

the heater for deliming.

prepare the up-n-down transfer KIt

The next step is the preparation on the Up-N-Down Transfer Kit, if

you have not already done so:
1. With the 5 gallon Up-N-Down container in the vertical position,

unscrew the plastic vent cap in the handle and pierce the

plastic membrane over the vent boss under the cap to allow the

container to vent.

note: If your container does not have the vent cap and vent

boss, drill a 3/16” (4.76mm) hole in the handle. When you have

finished deliming you will be able to plug this drilled vent with the

stainless steel screw that is supplied with the kit.

2. Remove the container’s cap and cut plastic membrane located in

the 3/4” IPT opening in cap. Take care to not damage the threads.

3. Find the 3/4” male adapter, apply teflon tape to the threaded end

and screw it into the 3/4” IPT opening in the cap.

This manual is related to the following products: