beautypg.com

Explosion hazard – State SBS100 76NE User Manual

Page 11

background image

11

water pIpInG

water (potable) heatInG and space heatInG

This water heater shall not be connected to any heating systems

or component(s) used with a non-potable water heating appliance.

All piping components connected to this unit for space heating

applications shall be suitable for use with potable water.

Toxic chemicals, such as those used for boiler treatment shall not

be introduced into this system.

When the system requires water for space heating at temperatures

higher than required for domestic water purposes, a mixing valve

must be installed. Please refer to Figure 2 for suggested piping

arrangement.

These water heaters cannot be used in space heating applications

only.

closed water sYsteMs

Water supply systems may, because of code requirements or

such conditions as high line pressure, among others, have

installed devices such as pressure reducing valves, check

valves, and back flow preventers. Devices such as these cause

the water system to be a closed system.

therMal expansIon

As water is heated, it expands (thermal expansion). In a closed

system the volume of water will grow when it is heated. As the

volume of water grows there will be a corresponding increase in

water pressure due to thermal expansion. Thermal expansion

can cause premature tank failure (leakage). This type of failure

is not covered under the limited warranty. Thermal expansion

can also cause intermittent Temperature-Pressure Relief Valve

operation: water discharged from the valve due to excessive

pressure build up. This condition is not covered under the limited

warranty. The Temperature-Pressure Relief Valve is not intended

for the constant relief of thermal expansion.
A properly sized thermal expansion tank must be installed on

all closed systems to control the harmful effects of thermal

expansion. Contact a local plumbing service agency to have a

thermal expansion tank installed.

fIGure 7.

NOTE: To protect against untimely corrosion of hot and cold

water fittings, it is strongly recommended that di-electric unions

or couplings be installed on this water heater when connected to

copper pipe.
Figure 7 shows the typical attachment of the water piping to the

water heater. The water heater is equipped with 1” NPT threaded

nipple (75 gallon models) or 1.25” NPT threaded nipple (100

gallon models) water connections.

teMperature-pressure relIef valve

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.
Can result in overheating and

excessive tank pressure.
Can cause serious injury or death.

This water heater is provided with a properly rated/sized and

certified combination Temperature-Pressure Relief Valve (T&P

valve) by the manufacturer. The valve is certified by a nationally

recognized testing laboratory that maintains periodic inspection

of production of listed equipment of materials as meeting the

requirements for Relief Valves for Hot Water Supply Systems,

ANSI Z21.22 • CSA 4.4, and the code requirements of ASME.
If replaced, the new T&P valve must meet the requirements of

local codes, but not less than a combination Temperature-Pressure

Relief Valve rated/sized and certified as indicated in the above

paragraph. The new valve must be marked with a maximum set

pressure not to exceed the marked hydrostatic working pressure

of the water heater (150 psi = 1,035 kPa) and a discharge capacity

not less than the water heater Btu/hr or kW input rate as shown

on the water heater’s model rating label.

This manual is related to the following products: