It is recommended that the Temperature-Pressure Relief Valve should

be checked to ensure that it is in operating condition every 6 months.
When checking the Temperature-Pressure Relief Valve operation,

make sure that (1) no one is in front of or around the outlet of the

Temperature-Pressure Relief Valve discharge line, and (2) that the

water discharge will not cause any property damage, as the water

may be extremely hot. Use care when operating valve as the valve

may be hot.
To check the relief valve, lift the lever at the end of the valve several

times, see Figure 20. The valve should seat properly and operate freely.
If after manually operating the valve, it fails to completely reset

and continues to release water, immediately close the cold

water inlet to the water heater and drain the water heater, see

Draining And Flushing on page 25. Replace the Temperature-

Pressure Relief Valve with a properly rated/sized new one, see

Temperature-Pressure Relief Valve on page 11 for instructions

on replacement.

DISCHARGE PIPE

TEMPERATURE-PRESSURE

RELIEF VALVE

fIGure 20.

If the Temperature-Pressure Relief Valve on the water heater

weeps or discharges periodically, this may be due to thermal

expansion.
note: Excessive water pressure is the most common cause of

Temperature-Pressure Relief Valve leakage. Excessive water

system pressure is most often caused by “thermal expansion”

in a “closed system.” See Closed Water Systems and Thermal

Expansion on page 10. The Temperature-Pressure Relief Valve is

not intended for the constant relief of thermal expansion.
Temperature-Pressure Relief Valve leakage due to pressure build

up in a closed system that does not have a thermal expansion

tank installed is not covered under the limited warranty. Thermal

expansion tanks must be installed on all closed water systems.
do not pluG the teMperature-pressure relIef

valve openInG. thIs can cause propertY daMaGe,

serIous InjurY or death.

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.
Can result in overheating and

excessive tank pressure.
Can cause serious injury or death.

recoMMended procedure for perIodIc

reMoval of lIMe deposIts froM tanK tYpe

coMMercIal water heaters

The amount of calcium carbonate (lime) released from water is in

direct proportion to water temperature and usage, see chart. The

higher the water temperature or water usage, the more lime deposits

are dropped out of the water. This is the lime scale which forms in

pipes, heaters and on cooking utensils.

houseKeepInG

Fire and Explosion Hazard

Do not obstruct combustion air

openings at the bottom of the

water heater.

Do not use or store flammable vapor

products such as gasoline, solvents

or adhesives in the same room or area

near water heater or other appliance.
Can cause serious injury or death.

Vacuum around base of water heater for dust, dirt, and lint on a

regular basis.
INSTALLED IN SUITABLE AREA: To insure sufficient ventilation

and combustion air supply, proper clearances from the water heater

must be maintained. See “Locating the New Water Heater” section.

Combustible materials such as clothing, cleaning materials, or

flammable liquids, etc. must not be placed against or adjacent to

the water heater which can cause a fire.

anode rod InspectIon

Property Damage Hazard

Avoid water heater damage.

Inspection and replacement of anode rod required.

CAUTION

The anode rod is used to protect the tank from corrosion. Most hot

water tanks are equipped with an anode rod. The submerged rod

sacrifices itself to protect the tank. Instead of corroding the tank,

water ions attack and eat away the anode rod. This does not affect

water’s taste or color. The rod must be maintained to keep the tank

in operating condition.
Anode deterioration depends on water conductivity, not necessarily

water condition. A corroded or pitted anode rod indicates high water

conductivity and should be checked and/or replaced more often than

an anode rod that appears to be intact. Replacement of a depleted

anode rod can extend the life of your water heater. Inspection should

be conducted by a qualified service agency, and at a minimum should

be checked annually after the warranty period.
Artificially softened water is exceedingly corrosive because the

process substitutes sodium ions for magnesium and calcium ions.
The use of a water softener may decrease the life of the water

heater tank.
The anode rod should be inspected after a maximum of three years

and annually thereafter until the condition of the anode rod dictates

its replacement.
note: Artificially softened water requires the anode rod to be

inspected annually.

teMperature-pressure relIef valve test

Burn hazard.

Hot water discharge.

Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.