beautypg.com

State SBS100 76NE User Manual

Page 13

background image

13

amount of combustion air can result in a fire or explosion and cause property

damage, serious bodily injury or death.

unconfIned space

An Unconfined Space is one whose volume is not less than 50

cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the

total input rating of all appliances installed in the space. Rooms

communicating directly with the space, in which the appliances

are installed, through openings not furnished with doors, are

considered a part of the unconfined space.
Makeup air requirements for the operation of exhaust fans, kitchen

ventilation systems, clothes dryers and fireplaces shall also be

considered in determining the adequacy of a space to provide

combustion, ventilation and dilution air.

unusuallY tIGht constructIon

In unconfined spaces in buildings, infiltration may be adequate to

provide air for combustion, ventilation and dilution of flue gases.

However, in buildings of unusually tight construction (for example,

weather stripping, heavily insulated, caulked, vapor barrier, etc.)

additional air must be provided using the methods described in

the Confined Space section that follows.

confIned space

A Confined Space is one whose volume is less than 50 cubic feet per

1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all

appliances installed in the space.
Openings must be installed to provide fresh air for combustion, ventilation

and dilution in confined spaces. The required size for the openings is

dependent on the method used to provide fresh air to the confined space

and the total Btu/hr input rating of all appliances installed in the space.

dIrect vent applIances

Appliances installed in a Direct Vent configuration that derive all

air for combustion from the outdoor atmosphere through sealed

intake air piping are not factored in the total appliance input Btu/hr

calculations used to determine the size of openings providing fresh

air into confined spaces.

exhaust fans

Where exhaust fans are installed, additional air shall be provided

to replace the exhausted air. When an exhaust fan is installed in

the same space with a water heater, sufficient openings to provide

fresh air must be provided that accommodate the requirements

for all appliances in the room and the exhaust fan. Undersized

openings will cause air to be drawn into the room through the water

heater’s vent system causing poor combustion. Sooting, serious

damage to the water heater and the risk of fire or explosion may

result. It can also create a risk of asphyxiation.

louvers and GrIlles

The free areas of the fresh air openings in the instructions that follow do not

take in to account the presence of louvers, grilles or screens in the openings.
The required size of openings for combustion, ventilation and dilution

air shall be based on the “net free area” of each opening. Where the

free area through a design of louver or grille or screen is known, it shall

be used in calculating the size of opening required to provide the free

area specified. Where the louver and grille design and free area are not

known, it shall be assumed that wood louvers will have 25% free area

and metal louvers and grilles will have 75% free area. Non motorized

louvers and grilles shall be fixed in the open position.

fresh aIr openInGs for confIned spaces

The following instructions shall be used to calculate the size,

number and placement of openings providing fresh air for

combustion, ventilation and dilution in confined spaces. The

illustrations shown in this section of the manual are a reference

for the openings that provide fresh air into confined spaces

only. Do not refer to these illustrations for the purpose of vent

installation. See Venting Installation on page 18 for complete

venting installation instructions.

outdoor aIr throuGh two openInGs

fIGure 8.

The confined space shall be provided with two permanent

openings, one commencing within 12 inches (300 mm) of the top

and one commencing within 12 inches (300 mm) of the bottom of

the enclosure. The openings shall communicate directly with the

outdoors. See Figure 8.
Each opening shall have a minimum free area of 1 square inch per

4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all

appliances installed in the enclosure. Each opening shall not be less

than 100 square inches (645 cm2).

outdoor aIr throuGh one openInG

fIGure 9.

Alternatively a single permanent opening, commencing within 12

inches (300 mm) of the top of the enclosure, shall be provided. See

Figure 9. The water heater shall have clearances of at least 1 inch

(25 mm) from the sides and back and 6 inches (150 mm) from the

front of the appliance. The opening shall directly communicate with

the outdoors or shall communicate through a vertical or horizontal duct

to the outdoors or spaces that freely communicate with the outdoors

and shall have a minimum free area of the following:
1. 1 square inch per 3000 Btu/hr (733 mm

2

per kW) of the total

input rating of all appliances located in the enclosure, and

2. Not less than the sum of the areas of all vent connectors in

the space.

This manual is related to the following products: