beautypg.com

Figure 30 (s, E 36) s, Installation – Outback Power Systems GS4048A Installation Manual User Manual

Page 38: Figure 30 parallel wiring

background image

Installation

36

900-0160-01-00 Rev A

Figure 30 Parallel Wiring

1. The Radian inverter has separate neutral connections for grid input, generator input, and output. These are electrically common. If an

external neutral bus exists (as shown in the AC Load Panel above), not all of the Radian neutral connections need to be made.

2. Maintenance bypass switching assemblies are commonly used so that the inverter can be taken offline, if necessary, without shutting

down the entire system. These assemblies usually include an interlock mechanism that isolates AC lines from each other. This figure

shows the general design of a bypass system.

3. When multiple inverters are stacked, the GS Load Center (GSLC) for each inverter can be wired together to serve as a common input

conduit box and AC load center. However, the GSLC bypass switching assemblies are only sized for single inverters and cannot work in

conjunction with each other. The GSLC bypass assemblies should not be used with multiple inverters present. (See page 10.) An
external bypass assembly must be used instead. Larger external assemblies are available from other manufacturers.

NOTES:

This manual is related to the following products: