Ac wiring, Ge 22 f, Installation – Outback Power Systems GS4048A Installation Manual User Manual
Page 24
Installation
22
AC Wiring
WARNING: Shock Hazard
The neutral and ground conductors should be mechanically bonded.
Ensure there is no more than one AC neutral-ground bond at any time.
Local or national codes may require the bond to be made at the main panel
only. The GS Load Center (GSLC) is equipped with its own bond, which may
need to be removed.
WARNING: Fire Hazard
Do not install the GS4048A using a load center that has multiwire branch circuits
connected.
CAUTION: Equipment Damage
The Radian inverter cannot be connected to a three-phase source (utility grid or
generator). The L1 and L2 inputs cannot be connected to two lines of a three-phase
power source.
IMPORTANT:
The installer is responsible for providing overcurrent protection. The AC input and
output must be protected with branch-rated circuit breakers of up to 50 Aac
maximum size to meet NEC or other code requirements.
All system wiring must comply with national and local codes and regulations.
The Radian inverter/charger’s AC terminal block has nine positions for AC wires. The minimum
recommended wire size is #8 AWG (0.013 in
2
) or 10 mm
2
. Larger wire gauges may be required for
specific conditions. The largest size that can be used with the terminals is #6 AWG (0.021 in
2
) or
16 mm
2
wire.
The inverter makes its AC connections using spring-loaded clamps. It is necessary to strip
approximately ½ inch (1.3 cm) of insulation from the end of each wire. Other tools are not required.
Figure 17 AC Terminals
AC Out
(L1, L2, Neutral)
Grid In
(L1, L2, Neutral)
Generator In (L1, L2, Neutral)