beautypg.com

Installation, Location and environmental requirements, Dimensions – Outback Power Systems GS4048A Installation Manual User Manual

Page 13

background image

900-0160-01-00 Rev A

11

Installation

Location and Environmental Requirements

Radian Series Inverter/Chargers must be located in a weather-proof enclosure or enclosed area. It is
not designed for exposure to water or excessive wind-blown dust and debris. It carries an Ingress

Protection (IP) rating of 20 and a Relative Humidity (RH) rating of 93%.
The Radian inverter must be wall-mounted in an upright position. The inverter is not approved for

mounting in any other position or orientation.

Recommended minimum clearance is 2 to 4 inches (5 to 10 cm) for the front and top of the inverter.

The sides and bottom may be enclosed or obscured with no restriction when mounting accessory devices or
one other Radian inverter. If more than two Radian inverters are installed side by side with the GSLC, the
inverters should be separated by at least 0.9 inches (2.3 cm) to accommodate the GSLC hinged doors.

The Radian inverter will function best if operated in a temperature range of -4°F to 77°F (–20°C to 25°C). At
temperatures up to 122°F (50°C), all inverter components meet their specifications, but the inverter’s power
is derated. It can function in environments as cold as –40°F (–40°C) and as warm as 140°F (60°C), but it may
not meet all component specifications. This temperature range also applies to storage.

The specifications are listed in the Radian Series Inverter/Charger Operator’s Manual.

Dimensions

Figure 6 Dimensions

Enclosure Height 28” (71.1 cm)

Mounting Hole Spacing 1.97" (5.0 cm)

Enclosure

Height with

Flange

29.1” (74 cm)

Width 16” (40.6 cm)

Depth

8.75"

(22 cm)

The dimensions of an assembled system with mounting plate and GSLC are shown on the next page.

This manual is related to the following products: