beautypg.com

Three-wire-start, D 29.), Installation – Outback Power Systems GS4048A Installation Manual User Manual

Page 31

background image

Installation

900-0160-01-00 Rev A

29

Three-Wire-Start

A “three-wire-start” generator has two or more starting circuits. It usually has a separate switch or

position for cranking the generator. A three-wire generator has fewer automated functions than a

two-wire. It usually requires multiple controls for starting, running, or stopping. The inverter

terminals cannot control this type of generator without using a three-wire to two-wire conversion kit.
Atkinson Electronics

(http://atkinsonelectronics.com) is one company that makes these kits. The

Atkinson GSCM-Mini is intended to work with OutBack inverters.
NOTE: The conversion kit requires a 12-volt signal which the RELAY AUX terminals cannot provide.
The

12V AUX terminals may be used to operate the conversion kit, as shown in Figure 25 .

If the

AUX terminals are being used for another purpose, it may be necessary for the RELAY AUX

terminals to control an external relay and 12-volt source in conjunction with the conversion kit. The
wiring and requirements for this arrangement will depend on the circumstances.

Figure 25 Three-Wire Generator Start (Example)

Atkinson

GSCM-Mini

Three-Wire-Start

Generator

12V AUX Terminals

This manual is related to the following products: