beautypg.com

Wiring, Grounding, E 20 – Outback Power Systems GS4048A Installation Manual User Manual

Page 21: E 19, Installation

background image

Installation

900-0160-01-00 Rev A

19

Wiring

It will be necessary to remove knockouts from the chassis to run wires. Bushings are included with the

hardware kit to protect the wires. Make sure to install these bushings in the holes.
Use copper wire only. Wire must be rated at 75°C or higher.

Grounding

WARNING: Shock Hazard

This unit meets the IEC requirements of Protection Class I.

The unit must be connected to a permanent wiring system that is grounded

according to the IEC 60364 TN standard.

The input and output circuits are isolated from ground. The installer is responsible

for system grounding according to all applicable codes.

For safety, the neutral and ground conductors should be mechanically bonded.

OutBack does not bond these conductors within the inverter. Make sure that no

more than one bond is present in the AC system at any time. Some codes require

the bond to be made at the main panel only.

The GS Load Center (GSLC) is equipped with a neutral-ground bond. If bonding is

required to be in another location, the bond in the GSLC may need to be removed.

WARNING: Shock Hazard

For all installations, the negative battery conductor should be bonded to the grounding

system at only one point. If the OutBack GFDI is present, it can provide the bond. (The
GSLC is also equipped with its own bond, which may need to be removed.)

IMPORTANT:

Most OutBack products are not designed for use in a positive-grounded system. If it is

necessary to build a positive-grounded system with OutBack products, contact OutBack
Technical Support at

+1.360.618.4363 before proceeding. Additionally, consult the

online forum at

www.outbackpower.com/forum/, where this subject has been

discussed extensively.

Table 3 Ground Conductor Size and Torque Requirements

Terminal Location

Minimum Conductor Size Torque Requirements

Ground TBB

#8 AWG (0.013 in²) or 10 mm²

25 in-lb (2.8 Nm)

Figure 14 Chassis Ground TBB

The inverter’s ground terminal bus bar (TBB) may be used for
making all ground connections to other parts of the system.

Examples include inverter equipment grounding, generator

grounding, load panel grounding, and main earth ground

wire. When the GSLC is used, make a connection from the

inverter to the ground TBB in the GSLC.
This TBB accepts up to #4 AWG (0.033 in²) or 25 mm² wire.

This manual is related to the following products: