Installation – Outback Power Systems GS4048A Installation Manual User Manual

Page 34

background image

Installation

32

900-0160-01-00 Rev A

Figure 27 Single-Inverter AC Wiring with GS Load Center

1. Ground wiring is not shown for reasons of simplicity. Regardless, this system must be connected to a grounded, permanent wiring

system. See page 19.

2. The Radian inverter has separate neutral connections for grid input, generator input, and output. These are electrically common. If an

external neutral bus exists (as shown in the GSLC), not all of the Radian neutral connections need to be made. In this example, only the

Grid neutral terminal on the inverter is connected.

3. The GSLC AC circuit breakers are designed as a maintenance bypass switching assembly. The assembly can be used so that the inverter

can be taken offline, if necessary, without shutting down the entire system. This figure shows the connections of a bypass system.