Specifications

900-0020-01-00 Rev B

47

The acceptance ranges are selected using the system display. In the MATE3, the options are

IEEE

and

user.

The

IEEE

option allows a range of 108 – 132 Vac at 59.3 – 60.5 Hz

The

user option does not have a fixed voltage setting. It follows the upper and lower limit settings in the

Grid AC Input Mode and Limits menu. The default is a range of 108 – 132 Vac.

Reconnection delay is 6 seconds. Sell delay is 5 minutes. These settings are not adjustable.

Firmware Revision

This manual applies to Radian series inverter/chargers with a firmware version of 001.004.xxx
or higher.

Default Settings and Ranges

Table 12 GS8048 Inverter Settings

Field

Item

Default

Minimum

Maximum

INVERTER

Hot Key Inverter Mode

Off

On, Off, or Search

CHARGER

Hot Key Charger Control

On

On or Off

AC Input

Hot Key

AC Input Mode

Use

Drop or Use

Search

Sensitivity (see page 16 for increments)

10

0

250

Pulse Length

8 AC cycles

4 AC cycles

20 AC cycles

Pulse Spacing

60 AC cycles

4 AC cycles

120 AC cycles

AC Input and
Current Limit

Input Priority

Grid

Grid or Gen

Grid Input AC Limit

50 Aac

5 Aac

55 Aac

Gen Input AC Limit

50 Aac

5 Aac

55 Aac

Charger AC Limit

30 Aac

0 Aac

30 Aac

Grid AC Input
Mode and Limits

Input Mode

Grid Tied

Generator, Support, Grid Tied, UPS, Backup,

Mini Grid

Voltage Limit Lower

108 Vac

70 Vac

110 Vac

(Voltage Limit)Upper

132 Vac

125 Vac

140 Vac

Transfer Delay

6 AC cycles

0 AC cycles

240 AC cycles

Connect Delay

0.2 minutes

0.2 minutes

15 minutes

Gen AC Input
Mode and Limits

Input Mode

Generator

Generator, Support, Grid Tied, UPS, Backup,

Mini Grid

Voltage Limit Lower

108 Vac

70 Vac

110 Vac

(Voltage Limit) Upper

140 Vac

125 Vac

140 Vac

Transfer Delay

6 AC cycles

0 AC cycles

240 AC cycles

Connect Delay

0.5 minutes

0.2 minutes

15 minutes

AC Output

Output Voltage

240 Vac

220 Vac

260 Vac

Low Battery

Cut-Out Voltage

42 Vdc

36 Vdc

48 Vdc

Cut-In Voltage

50 Vdc

40 Vdc

56 Vdc

Battery Charger

Absorb Voltage

57.6 Vdc

52 Vdc

64 Vdc

(Absorb) Time

1.0 hours

0.0 hours

24.0 hours

Float Voltage

54.4 Vdc

48 Vdc

60 Vdc

(Float) Time

1.0 hours

0.0 hours

24.0 hours

Re-Float Voltage

50 Vdc

48 Vdc

52 Vdc

Battery Equalize

Equalize Voltage

58.4 Vdc

56 Vdc

68 Vdc

(Equalize) Time

1.0 hours

0.0 hours

24.0 hours

Auxiliary Output

Aux Control

Off

Off, Auto or On