Troubleshooting

900-0020-01-00 Rev B

39

Table 3 Troubleshooting

Symptom

Possible Cause

Possible Remedy

Inverter hums

loudly. System

display may show

messages for high
battery voltage,

low battery voltage,

or backfeed error.

Inverter output is being fed

with an external AC source that

is out of phase.

Disconnect AC output wires. Turn the inverter off and then on. If

the problem clears, reconnect the AC output wires. If the

problem recurs when reconnected, an external AC source is

connected to the output.

Inverter has been incorrectly

stacked with another unit on
the same output. All units

come defaulted as master.

Check HUB ports and make certain the master inverter is plugged

into port 1.

MATE3 system display only: Check stacking settings in the

Inverter

Stacking menu. Only one master is allowed per system.

Generator, external

fan, etc. fails to start

when triggered by

AUX output.

AUX output is not connected.

Test the generator or device to confirm functionality. Test the

appropriate AUX terminals with a DVM. (If the RELAY AUX

terminals are in use, test for continuity. If the 12V AUX terminals
are in use, test for 12 Vdc.) If the proper results are present when

the menu indicates the function is

On (and the device still does

not work), then there is an external connection problem. If the

proper results are not present with the function

On , the AUX

circuit may be damaged. Contact OutBack Technical Support (see
inside front cover of this manual).

Wrong AUX terminals have

been programmed.

MATE3 system display only: Confirm that the AUX menu that was

programmed matches the terminals that are in use. The

Auxiliary

Output menu programs the 12V AUX terminals. The Auxiliary
Relay
menu programs the RELAY AUX terminals.

Wrong AUX terminals are in use.

If generator or external device requires 12 Vdc, confirm the 12V

AUX terminals have been connected. The RELAY AUX terminals
do not provide voltage.

Automatic

Generator Start fails

to trigger when

conditions are met

(or starts when
conditions are not

met).

MATE3 system display only: AGS

function does not work if a valid

input is present.

Check both inputs for a second AC source (utility grid). If the

inverter detects an acceptable AC source, it will not allow AGS.

This is true even if it is internally disconnected from the source

(due to HBX mode,

Mini Grid mode, or similar programming).

MATE3 system display is not

present.

AGS programming is located in MATE3 and cannot function if it is

removed.


Module Select

The GS8048 uses two high-frequency H-Bridge FET modules. The dual design allows half the inverter

to shut down for lower idle consumption. Normally this is automatically selected. If one module fails

or if troubleshooting is otherwise needed, the module selection can be performed manually. The

GS8048 can be directed to use a single, specified module (left or right), or it can be directed to turn on

both modules continuously. This procedure should only be performed if directed by OutBack
Technical Support (see inside the front cover of this manual).
The Module Select menu options are displayed as part of the table of defaults, which begins on

page 47.