e. Troubleshooting Flowchart - Quick Reference...

Second Visual Check

(Does Main Burner Ignite?)

Does

main burner

light?

Is manual

knob on the Gas Valve

in the “ON”

position?

Is

dryer Internal Gas

Shut-Off Valve and

ALL External Gas Shut-Off

Valves in the open

position?

Go To

Third Visual

Check

Yes

Yes

Turn

manual knob on

the Gas Valve to the

“ON” position.

Energize the system.

Is outlet pressure

detected?

With

system energized,
is 24 VAC present

across the “MV” and “GND”

terminals of the DSI

Module?

Replace the Gas Valve.
Energize the system and
check for proper operation.

Turn manual knob on the Gas Valve to the
“OFF” position.
Connect a manometer to the Gas Valve
outlet pressure tap.

Yes

Replace High

Voltage (HV)

leads

Yes

Energize system

and check for

proper operation.

Replace

DSI Module

No

Energize

system. Is 24 VAC

present across leads

at the Gas

Valve?

No

Yes

Is

gas available

at the

source?

Yes

Restore gas supply.
Energize system and
check for proper
operation.

No

Check Spark Electrode for
proper gap and insure that
the spark is in the path of
the gas flow...
Refer To Service Section.

Is outlet

Water Column (W.C.)

pressure correct?

Natural 3.5” - 4.0” W.C.

(8.7 mb - 9.9 mb)

L.P. 10.5” - 11.0” W.C.

(26.1 mb - 27.4 mb)

Yes

No

Make the necessary
corrections.
Energize system and
check for proper operation.

Yes

Correct supply pressure.
Energize system and
check for proper operation

.

No

Turn knob to “ON/OPEN”
position.
Energize system and
check for proper operation.

No

No

No