Troubleshooting Flowchart - Quick Reference...

Second Visual Check

Spark Present But Main Burner Does Not Come On

Is main valve wiring securely

attached to terminal M.V.3

and ground?

No Yes

Is 24 VAC present

between terminals M.V.3

and ground ?

No Yes

Check for continuity in

wiring from M.V.3 to gas

valve, and gas valve to GR.

No Yes

Is inlet gas pressure per

manufacturer's specifications?

No Yes

Is Spark gap .125 in.

and in gas stream?

No Yes

Correct

Replace

Johnson Control

module G760/761

Correct

Correct

Determine

why continuity

does not exist.

Replace

gas valve.