Tighten the screws to secure the wire in the connector. Do not tighten the screws excessively;
doing so may strip the threads and damage the connector.
Wiring guidelines
The AXB-TPI/3 requires 12 VDC power to operate properly. Each module adds 500 mA of current
consumption (in addition to the baseline 630 mA for a stand-alone unit) on the TPI/3 system. The
unit should only have one source of incoming power.
Using the AXlink connector for data and power
To use the AXlink 4-pin connector for data communication with the Central Controller and power
transfer from the PSN6.5 power supply, the incoming PWR and GND cable from the PSN6.5 must
be connected to the AXlink cable connector going to the Central Controller. FIG. 18 shows the
AXlink wiring diagram. Always use a local power supply to power the TPI/3 unit.
Wiring Guidelines - No Module
Wiring Guidelines - One Module
Wire size
Maximum wiring length
Wire size
Maximum wiring length
18 AWG
186.30 feet (56.78 meters)
18 AWG
103.87 feet (31.66 meters)
20 AWG
117.87 feet (35.93 meters)
20 AWG
65.72 feet (20.03 meters)
22 AWG
73.49 feet (22.40 meters)
22 AWG
40.97 feet (12.49 meters)
24 AWG
46.32 feet (14.12 meters)
24 AWG
25.83 feet (7.87 meters)
Wiring Guidelines - Two Modules
Wiring Guidelines - Three Modules
Wire size
Maximum wiring length
Wire size
Maximum wiring length
18 AWG
72.01 feet (21.95 meters)
18 AWG
55.10 feet (16.79 meters)
20 AWG
45.56 feet (13.89 meters)
20 AWG
34.86 feet (10.63 meters)
22 AWG
28.40 feet (8.66 meters)
22 AWG
21.74 feet (6.63 meters)
24 AWG
17.90 feet (5.46 meters)
24 AWG
13.70 feet (4.18 meters)
Using more than one source of power to the AXB-TPI/3 can result in damage to the
internal components and a possible burn out.
FIG. 18 AXlink connector wiring diagram
PWR (+)
GND (-)
Local +12 VDC power supply
(coming from the PSN power supply)
PWR +
AXP/TX
AXM/RX
GND -
PWR +
AXP/TX
AXM/RX
GND -
To the Central Controller
To the AXB-TPI/3
Do not connect the wire from the PWR terminal on the Central Controller to the PWR
terminal on the TPI/3 unit when you connect an external power supply. Make sure to
connect only the AXM, AXP, and GND wires on the TPI/3’s AXlink connector when
using the PSN6.5 power supply.