Chapter 7 specifications, Specifications – HP Tower Uninterruptible Power System User Manual
Page 31

HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide
S 505922-002
24
Chapter 7
Specifications
This section provides the following specifications:
S
Model list
S
Dimensions and weights
S
Electrical input and output
S
Environmental and safety
S
Battery
Table 3
Model List
100V Models
120V Models
230V Models
UPS Models
HP T750J (HSTNR-U017-N)
HP T1000J (HSTNR-U018-N)
HP T1500J (HSTNR-U018-J)
HP T750 G2 (HSTNR-U016-N)
HP T1000 G3 (HSTNR-U017-N)
HP T1500 G3 (HSTNR-U018-N)
HP T750 G2 (HSTNR-U016-I)
HP T1000 G3 (HSTNR-U017-I)
HP T1500 G3 (HSTNR-U018-I)
Table 4
Dimensions and Weights
100V Models
120V Models
230V Models
UPS Dimensions
(W
H
D)
HP T750 G2, HP T750J, and HP T1000 G3: 15.0
19.3
33.5 cm (5.9
”
7.6
”
13.2
”)
HP T1000J, HP T1500 G3, and HP T1500J: 15.0
19.3
39.0 cm (5.9
”
7.6
”
15.4
”)
UPS Weights
HP T750 G2: 12.4 kg (27.3 lb)
HP T750J and HP T1000 G3: 12.6 kg (27.8 lb)
HP T1000J and HP T1500 G3: 16.8 kg (37.0 lb)
HP T1500J: 17.2 kg (37.9 lb)
Table 5
Electrical Input
100V Models
120V Models
230V Models
Nominal Voltage
100V
110V, 120V selectable
220V, 230V, 240V selectable
Voltage Range
±20% for nominal voltage at full load
Nominal Frequency
45–65 Hz, 50/60 Hz auto-sensing
Efficiency (Normal mode)
95%
Noise Filtering
Full-time EMI/RFI filtering
Overcurrent Protection
Resettable input overcurrent protector
N/A
Connections
6-ft, 5-15P power cord (90° angle)
10A, IEC-320 input connector