Power protection specifications, Output tolerance specifications, Output feature specifications – HP Tower Uninterruptible Power System User Manual
Page 60
Specifications 60
UPS model
Load segment
Output receptacles
2
2 x 5-20T
R/T3000h NA/JPN
1
3 x IEC-320-C13
1 x IEC-320-C19
1 x L6-20R
2
3 x IEC-320-C13
1 x IEC-320-C19
R/T3000 INTL
1
3 x IEC-320-C13
1 x IEC-320-C19
2
3 x IEC-320-C13
1 x IEC-320-C19
Power protection specifications
UPS model
VA
Nominal power rating
(W)
Nominal voltage
setting
R/T3000
NA/JPN
2880
2700
100, 110, 120, 127
R/T3000h
NA/JPN
3300
3000
204, 220, 230, 240
R/T3000 INTL
3300
3000
204, 220, 230, 240
Output tolerance specifications
Source of power
Regulation
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer
Business Equipment Manufacturers
Association)
Battery power
±5% of nominal output voltage rating
Output feature specifications
Feature
Specification
Online efficiency
94% nominal input voltage
Voltage wave shape
Sine wave; 5% THD with typical PFC load
Surge suppression
300J via MOVs
Noise filtering
EN 55022 line filter for normal and common mode
use